Measurement of IEC groups and subgroups using advanced spectrum estimation methods

被引:51
作者
Bracale, Antonio [1 ]
Carpinelli, Guido [1 ]
Leonowicz, Zbigniew [2 ]
Lobos, Tadeusz [2 ]
Rezmer, Jacek [2 ]
机构
[1] Univ Naples Federico II, Dept Elect Engn, I-80100 Naples, Italy
[2] Wroclaw Univ Technol, Dept Elect Engn, PL-50370 Wroclaw, Poland
关键词
DC arc furnaces; discrete Fourier transform (DFT); estimation of signal parameters via the rotational invariance techniques (ESPRIT) method; Prony method; root MUltiple-SIgnal Classification (MUSIC) method; spectrum estimation; subspace methods; waveform-distortion analysis;
D O I
10.1109/TIM.2007.911701
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The International Electrotechnical Commission (IEC) standards characterize the waveform distortions in power systems with the amplitudes of harmonic and interharmonic groups and subgroups. These groups/subgroups utilize the wave-form spectral components obtained from a fixed frequency-resolution discrete Fourier transform (DFT). Using the IEC standards allows for a compromise among the different goals, such as the needs for accuracy, simplification, and unification. In some cases, however, the power-system waveforms are characterized by spectral components that the DFT cannot capture with enough accuracy due to the fixed frequency resolution and/or the spectral leakage phenomenon. This paper investigates the possibility of a group/subgroup evaluation using the following advanced spectrum estimation methods: adaptive Prony, estimation of signal parameters via rotational invariance techniques, and root MUltiple-SIgnal Classification (MUSIC). These adaptive methods use variable lengths of time windows of analysis to ensure the best fit of the waveforms; they are not characterized by the fixed frequency resolution and do not suffer from the spectral leakage phenomenon. This paper also presents the results of the applications of these methods to three test waveforms, to current and voltage waveforms obtained from simulations of a real dc arc-furnace plant, and to waveforms measured at the point of common coupling of the low-voltage network supplying a high-performance laser printer.
引用
收藏
页码:672 / 681
页数:10
相关论文
共 17 条
[1]  
[Anonymous], 61000430 IEC
[2]  
[Anonymous], 2002, IEC 61000-4-7:2002
[3]   Accurate methods for signal processing of distorted waveforms in power systems [J].
Bracale, A. ;
Carpinelli, G. ;
Langella, R. ;
Testa, A. .
EURASIP JOURNAL ON ADVANCES IN SIGNAL PROCESSING, 2007, 2007 (1)
[4]   Adaptive Prony method for waveform distortion detection in power systems [J].
Bracale, A. ;
Caramia, P. ;
Carpinelli, G. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2007, 29 (05) :371-379
[5]  
BRACALE A, 2004, P 11 ICHQP LAK PLAC, P266
[6]  
Bracale A., 2007, INT J POWER ENERGY S, V27
[7]  
BRACALE A, 2004, P 11 ICHQP LAK PLAC, P260
[8]   Measurement of IEC groups and subgroups using advanced spectrum estimation methods [J].
Bracale, Antonio ;
Carpinelli, Guido ;
Leonowicz, Zbigniew ;
Lobos, Tadeusz ;
Rezmer, Jacek .
2006 IEEE INSTRUMENTATION AND MEASUREMENT TECHNOLOGY CONFERENCE PROCEEDINGS, VOLS 1-5, 2006, :1015-+
[9]   Chaos-based modeling of DC arc furnaces for power quality issues [J].
Carpinelli, G ;
Iacovone, F ;
Russo, A ;
Varilone, P .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (04) :1869-1876
[10]   Pain and performance: Are opioids the answer? [J].