Experimental research and operation optimization of an air-source heat pump water heater

被引:92
作者
Guo, J. J. [1 ]
Wu, J. Y. [1 ]
Wang, R. Z. [1 ]
Li, S. [1 ]
机构
[1] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Shanghai 200240, Peoples R China
关键词
Air-source heat pump water heater; Experimental research; Optimization; ENERGY-CONSUMPTION; PERFORMANCE ANALYSIS; SYSTEM DRIVEN; BUILDINGS; SECTOR; SPACE;
D O I
10.1016/j.apenergy.2011.04.012
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In order to optimize design and operation strategy of air-source heat pump water heater, an experimental set-up and simulation model were constructed. Also, a methodology of optimizing operation, which takes into account thermostatic and timing control patterns, was presented and applied. Experimental results indicated that the average COP ranged from 2.82 to 5.51 under typical conditions. The recommended outside area ratio of condenser coil to evaporator is 0.14-0.31 when the evaporator outside area is between 6.0 and 6.5 m(2) for this set-up. The optimal start-up time was between 12:00 and 14:00 if there was no electricity price difference between day and night, or it was near 22:00. The optimal setting water temperature should be adjusted according to the variation of seasonal ambient temperature. It was suggested that, based on this set-up, setting water temperature should be set higher than 46 degrees C in summer and 50 degrees C in other seasons. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:4128 / 4138
页数:11
相关论文
共 33 条
[1]   Modeling of the space and domestic hot-water heating energy-consumption in the residential sector using neural networks [J].
Aydinalp, M ;
Ugursal, VI ;
Fung, AS .
APPLIED ENERGY, 2004, 79 (02) :159-178
[2]   Energy consumption modeling of air source electric heat pump water heaters [J].
Bourke, Grant ;
Bansal, Pradeep .
APPLIED THERMAL ENGINEERING, 2010, 30 (13) :1769-1774
[3]   RETRACTED: A novel configuration and performance for a two-stage thermoelectric heat pump system driven by a two-stage thermoelectric generator (Retracted Article) [J].
Chen, L. ;
Meng, F. ;
Sun, F. .
PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART A-JOURNAL OF POWER AND ENERGY, 2009, 223 (A4) :329-339
[4]   Modeling and application of direct-expansion solar-assisted heat pump for water heating in subtropical Hong Kong [J].
Chow, T. T. ;
Pei, G. ;
Fong, K. F. ;
Lin, Z. ;
Chan, A. L. S. ;
He, M. .
APPLIED ENERGY, 2010, 87 (02) :643-649
[5]   Advances in heat pump systems: A review [J].
Chua, K. J. ;
Chou, S. K. ;
Yang, W. M. .
APPLIED ENERGY, 2010, 87 (12) :3611-3624
[6]   Determination of optimum working conditions R22 and R404A refrigerant mixtures in heat-pumps using Taguchi method [J].
Comakli, K. ;
Simsek, F. ;
Comakli, O. ;
Sahin, B. .
APPLIED ENERGY, 2009, 86 (11) :2451-2458
[7]  
*ENV, 2001, 129772 ENV
[8]  
European Commission, 2002, MAND CEN CENELEC EL
[9]  
GROLL EA, 2001, CLIM 2000 NAP IT
[10]   The performance of a solar assisted heat pump water heating system [J].
Hawlader, MNA ;
Chou, SK ;
Ullah, MZ .
APPLIED THERMAL ENGINEERING, 2001, 21 (10) :1049-1065