Indoor air quality impacts of ventilation ducts: Ozone removal and emissions of volatile organic compounds

被引:59
作者
Morrison, GC
Nazaroff, WW
Cano-Ruiz, JA
Hodgson, AT
Modera, MP
机构
[1] Univ Calif Berkeley, Dept Civil & Environm Engn, Berkeley, CA 94720 USA
[2] MIT, Dept Chem Engn, Cambridge, MA 02139 USA
[3] Ernest Orlando Lawrence Berkeley Natl Lab, Berkeley, CA USA
来源
JOURNAL OF THE AIR & WASTE MANAGEMENT ASSOCIATION | 1998年 / 48卷 / 10期
关键词
D O I
10.1080/10473289.1998.10463740
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The concentrations of contaminants in the supply air of mechanically ventilated buildings may be altered by pollutant emissions from and interactions with duct materials. We measured the emission rate of volatile organic compounds (VOCs) and aldehydes from materials typically found in ventilation ducts. The emission rate of VOCs per exposed surface area of materials was found to be low for some duct liners, but high for duct sealing caulk and a neoprene gasket. For a typical duct, the contribution to VOC concentrations is predicted to be only a few percent of common indoor levels. We exposed selected materials to similar to 100-ppb ozone and measured VOC emissions. Exposure to ozone increased the emission rates of aldehydes from a duct liner, duct sealing caulk, and neoprene gasket. The emission of aldehydes from these materials could increase indoor air concentrations by amounts that are as much as 20% of odor thresholds. We also measured the rate of ozone uptake on duct liners and galvanized sheet metal to predict how much ozone might be removed by a typical duct in ventilation systems. For exposure to a constant ozone mol fraction of 37 ppb, a lined duct would initially remove similar to 9% of the ozone, but over a period of 10 days the ozone removal efficiency would diminish to less than 4%. In an unlined duct, in which only galvanized sheet metal is exposed to the airstream, the removal efficiency would be much lower, similar to 0.02%. Therefore, ducts in ventilation systems are unlikely to be a major sink for ozone.
引用
收藏
页码:941 / 952
页数:12
相关论文
共 32 条
[1]  
Batterman A.S., 1995, RES HVACR, V1, P61, DOI [10.1080/10789669.1995.10391309, DOI 10.1080/10789669.1995.10391309]
[2]   THEORY OF HEAT-TRANSFER FROM A SURFACE COVERED WITH HAIR [J].
BEJAN, A .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1990, 112 (03) :662-667
[3]  
Bhatti M.S., 1987, HDB SINGLE PHASE CON
[4]   CONCENTRATIONS OF VOLATILE ORGANIC-COMPOUNDS IN INDOOR AIR - A REVIEW [J].
BROWN, SK ;
SIM, MR ;
ABRAMSON, MJ ;
GRAY, CN .
INDOOR AIR-INTERNATIONAL JOURNAL OF INDOOR AIR QUALITY AND CLIMATE, 1994, 4 (02) :123-134
[5]   SICK BUILDING SYNDROME - A STUDY OF 4373 OFFICE WORKERS [J].
BURGE, S ;
HEDGE, A ;
WILSON, S ;
BASS, JH ;
ROBERTSON, A .
ANNALS OF OCCUPATIONAL HYGIENE, 1987, 31 (04) :493-504
[6]   REMOVAL OF REACTIVE GASES AT INDOOR SURFACES - COMBINING MASS-TRANSPORT AND SURFACE KINETICS [J].
CANORUIZ, JA ;
KONG, D ;
BALAS, RB ;
NAZAROFF, WW .
ATMOSPHERIC ENVIRONMENT PART A-GENERAL TOPICS, 1993, 27 (13) :2039-2050
[7]  
CANORUIZ JA, 1992, P 13 AIR INF VENT C, P217
[8]   PROTECTION OF WORKS OF ART FROM DAMAGE DUE TO ATMOSPHERIC OZONE [J].
CASS, GR ;
NAZAROFF, WW ;
TILLER, C ;
WHITMORE, PM .
ATMOSPHERIC ENVIRONMENT PART A-GENERAL TOPICS, 1991, 25 (02) :441-451
[9]  
Davies J.T., 1972, TURBULENCE PHENOMENA
[10]  
Devos M., 1990, STANDARDIZED HUMAN O