Thermal analysis of cast-resin dry-type transformers

被引:64
作者
Eslamian, M. [1 ]
Vahidi, B. [1 ]
Eslamian, A. [2 ]
机构
[1] Amir Kabir Univ Technol, Dept Elect Engn, Tehran, Iran
[2] Islamic Azad Univ, Dept Engn, Zanjan Branch, Zanjan, Iran
关键词
Cast-resin dry-type transformer; Thermal modeling; FEM; CFD; HOTTEST SPOT TEMPERATURES;
D O I
10.1016/j.enconman.2011.02.006
中图分类号
O414.1 [热力学];
学科分类号
摘要
Non-flammable characteristic of dry-type cast-resin transformers make them suitable for residential and hospital usages. However, because of resin's property, thermal behavior of these transformers is undesirable, so it is important to analyze their thermal behavior. In this paper temperature distribution of cast-resin transformers is modeled by two different approaches. A FEM-based model which uses experimental-analytical formula for air-cooling vertical ducts and a 3D finite volume based CFD model which is established in the ANSYS CFX software. In order to evaluate and compare the models, the simulation results were compared with the experimental data measured from an 800 kVA transformer. Finally, the influences of some construction parameters and environmental conditions on temperature distribution of cast-resin transformers were discussed. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2479 / 2488
页数:10
相关论文
共 12 条
[1]  
[Anonymous], 1991, EQUATIONS MOTION REA
[2]  
Halacsy A. A., 1958, AIEE T 3, V77, P456
[3]  
HOLMAN JF, 1934, HEAT TRANSFER
[4]  
Incropera F.P., 2001, Introduction to Heat Transfer
[5]  
Meeker D., 2006, Finite Element Method Magnetics-Version 4.0 User's Manual
[6]  
NUNN T, 2000, COMP LIQUID FILLED D, P105
[7]   HOTTEST SPOT TEMPERATURES IN VENTILATED DRY-TYPE TRANSFORMERS [J].
PIERCE, LW .
IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (01) :257-263
[8]   PREDICTING HOTTEST SPOT TEMPERATURES IN VENTILATED DRY-TYPE TRANSFORMER WINDINGS [J].
PIERCE, LW .
IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (02) :1160-1172
[9]  
Satterlee W.W., 1944, AIEE T, P701
[10]  
STEWART HC, 1944, AIEE T, V63, P763