Responses of resistive superconducting-fault-current-limiters to unbalanced faults

被引:17
作者
Choi, HS [1 ]
Lim, SH
Chung, DC
Han, BS
Hyun, OB
Sung, TH
Hwang, JS
机构
[1] Chosun Univ, Dept Elect Engn, Kwangju 501759, South Korea
[2] Chobuk Natl Uni, Inst Engn Res, Res Ctr Ind Technol, Jeonju 561756, South Korea
[3] Woosuk Univ, Dept Informat Engn, Jeonbuk 565701, Wanju, South Korea
[4] Chonbuk Natl Univ, Sch Elect & Informat Engn, Jeonju 561756, South Korea
[5] Korea Elect Power Res Inst, Taejon 305380, South Korea
[6] Namdo Provincial Coll, Damyang 517802, South Korea
关键词
fault current limiter; the sequence current; unbalanced fault; unsymmetrical characteristic;
D O I
10.1109/TASC.2005.849445
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
We analyzed the unsymmetrical fault characteristics of resistive superconducting-fault-current-limiters (SFCL) based on YBCO thin films with the unbalanced faults such as a single line-to-ground fault, a double line-to-ground fault, and a fine-to-line fault in a three-phase system. The unsymmetrical rates of fault phases were 6.4, 9.2, 8.8 at the fault onset, but decreased by 1.4, 1.5, 3.7 after 50 ms in the fault types, respectively. The positive sequence current I-1 was the highest in a double line-to-ground fault, immediately after the fault onset, but that of a line-to-line fault was the highest after 50 ms. This means the current limiting effect was the worst in a line-to-line fault, due to the unbalanced quench between the SFCL units. The negative sequence currents I-2 of a single and double line-to-ground faults were relatively low, except for the quench instant, because of the rapid interruption of fault currents by the SFCL. The zero sequence current I-0 was similar to the behavior of the negative sequence current. Finally, the positive sequence resistance Z(1) was reduced remarkably immediately after the fault but gradually approached the balanced positive sequence resistance prior to the system fault, except during a line-to-line fault. The simultaneous quench between the SFCL units was important for low line-to-line fault currents.
引用
收藏
页码:2035 / 2038
页数:4
相关论文
共 10 条
[1]   Quench characteristics of resistive superconducting fault current limiters based on YBa2Cu3O7 films [J].
Choi, HS ;
Hyun, OB ;
Kim, HR .
PHYSICA C, 2001, 351 (04) :415-420
[2]   Manufacturing and testing of MCP 2212 bifilar coils for a 10 MVA fault current limiter [J].
Elschner, S ;
Breuer, F ;
Noe, M ;
Rettelbach, T ;
Walter, H ;
Bock, J .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2003, 13 (02) :1980-1983
[3]   Resistive fault current limiters with YBCO films - 100 kVA functional model [J].
Gromoll, B ;
Ries, G ;
Schmidt, W ;
Kraemer, HP ;
Seebacher, B ;
Utz, B ;
Nies, R ;
Neumueller, HW ;
Baltzer, E ;
Fischer, S ;
Heismann, B .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 1999, 9 (02) :656-659
[4]   DC reactor effect on bridge type superconducting fault current limiter during load increasing [J].
Hoshino, T ;
Salim, KM ;
Nishikawa, M ;
Muta, I ;
Nakamura, T .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2001, 11 (01) :1944-1947
[5]  
JOO M, 1999, IEEE T APPL SUPERCON, V9, P4613
[6]   The fault current limiting characteristics of a flux-lock type high-Tc superconducting fault current limiter using series resonance [J].
Lim, SH ;
Choi, HS ;
Han, BS .
CRYOGENICS, 2004, 44 (04) :249-254
[7]   Performance of an inductive fault current limiter employing BSCCO superconducting cylinders [J].
Meerovich, V ;
Sokolovsky, V ;
Bock, J ;
Gauss, S ;
Goren, S ;
Jung, G .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 1999, 9 (04) :4666-4676
[8]   Technical and economical benefits of superconducting fault current limiters in power systems [J].
Noe, M ;
Oswald, BR .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 1999, 9 (02) :1347-1350
[9]   Waveform analysis of the bridge type SFCL during load changing and fault time [J].
Salim, KM ;
Hoshino, T ;
Kawasaki, A ;
Muta, I ;
Nakamura, T .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2003, 13 (02) :1992-1995
[10]   Improved design and system approach of a three phase inductive HTS fault current limiter for a 12 kVA synchronous generator [J].
Vajda, I ;
Györe, A ;
Szalay, A ;
Sokolovsky, V ;
Gawalek, W .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2003, 13 (02) :2000-2003