Buoyancy and inertial force on oscillations of thermal-induced convective flow across a vent

被引:19
作者
Chow, W. K. [1 ]
Gao, Y. [2 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Kowloon, Hong Kong, Peoples R China
[2] Harbin Engn Univ, Dept Bldg Engn, Harbin, Heilongjiang, Peoples R China
关键词
Vent; Buoyancy; Expansion pressure; Thermal-induced flow; OPEN-ENDED CAVITIES; PRESSURE;
D O I
10.1016/j.buildenv.2010.07.023
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Natural vents are commonly installed in buildings for smoke control. Air motion is induced by buoyancy of the thermal sources inside the building. Hot smoke is expected to be exhausted out of the vent. However, directions of air flowing across the vent might be oscillating under some conditions. The ratio B of buoyancy to inertial force defined by the Grashof number over the square of the Reynolds number is the key parameter in determining airflow oscillations. In this paper, effects of buoyancy, pressure, and the combined effect of buoyancy and pressure denoted by B will be studied by simple flow equations. A room fire with a horizontal vent is taken as an example. The results indicate that pressure is the driving force for the airflow oscillations when B < 0.1. Buoyancy is the dominating factor when B > 10. However, the combined effect of pressure and buoyancy is important when B is close to 1. Results are useful for designing smoke exhaust systems with natural vents. (C) 2010 Elsevier Ltd. All rights reserved.
引用
收藏
页码:315 / 323
页数:9
相关论文
共 15 条
[1]   NONACOUSTIC COMBUSTOR INSTABILITY [J].
BECKSTEA.MW ;
PRICE, EW .
AIAA JOURNAL, 1967, 5 (11) :1989-+
[2]  
CHOW WK, 2004, REFRIGERATING AIR CO, V110, P479
[3]   COMBINED BUOYANCY AND PRESSURE-DRIVEN FLOW-THROUGH A SHALLOW, HORIZONTAL, CIRCULAR VENT [J].
COOPER, LY .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1995, 117 (03) :659-667
[4]   BUOYANCY-DRIVEN EXCHANGE FLOW THROUGH SMALL OPENINGS IN HORIZONTAL PARTITIONS [J].
EPSTEIN, M .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1988, 110 (4A) :885-893
[5]   NON-DARCIAN EFFECTS IN OPEN-ENDED CAVITIES FILLED WITH A POROUS-MEDIUM [J].
ETTEFAGH, J ;
VAFAI, K ;
KIM, SJ .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1991, 113 (03) :747-756
[6]   AN INVESTIGATION OF EJECTION, MIXING, AND SUCTION MECHANISMS IN AN OPEN-ENDED HORIZONTAL ANNULUS [J].
ETTEFAGH, J ;
VAFAI, K .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1991, 113 (04) :1025-1028
[7]  
ETTEFAGH J, 2000, INT J HEAT MASS TRAN, V43, P4087
[8]  
JALURIA Y, NEGATIVELY BUOYANT W
[9]   A two-dimensional numerical investigation of the oscillatory flow behaviour in rectangular fire compartments with a single horizontal ceiling vent [J].
Kerrison, L ;
Galea, ER ;
Patel, MK .
FIRE SAFETY JOURNAL, 1998, 30 (04) :357-382
[10]  
Li J., 2002, J APPL FIRE SCI, V11, P229, DOI DOI 10.2190/RK04-K8TA-1J92-E0F0