Fuzzy detection of high impedance faults in radial distribution feeders

被引:17
作者
Jota, PRS [1 ]
Jota, FG [1 ]
机构
[1] CEFET MG, Fed Ctr Technol Educ, Dept Elect Engn, BR-30510000 Belo Horizonte, MG, Brazil
关键词
high impedance fault; neural networks; radial distribution feeders;
D O I
10.1016/S0378-7796(98)00116-3
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The paper presents a methodology for the detection of high impedance faults in radial distribution feeders. The technique consists of making comparative analysis of the responses of the feeder to pulses injected at the feeder inlet for different configurations. The responses to normal configurations constitute the set, hereafter called 'standard responses', of the feeder under test. An artificial neuron set, composed of 'neo-fuzzy' neurons, is trained to recognize the standard responses. After the training period, the neuron-set becomes the decision core of the supervisory system. Subsequently, the supervisory system is used to monitor the feeder in real time. The feeder responses are periodically analysed by the neuron-set, which classifies them according to the 'pre-defined' standard responses. In this way, non-standard configurations are not classified. Simulation and experimental studies have shown that the proposed system is capable of recognizing passive high impedance faults even when they occur close to a switch (used to change configuration). In order to corroborate the efficiency of the proposed methodology, experimental tests have been accomplished in a real feeder. They have shown satisfactory results. (C) 1999 Elsevier Science S.A. All rights reserved.
引用
收藏
页码:169 / 174
页数:6
相关论文
共 12 条
[1]  
Arrillaga J., 1985, Power System Harmonics
[2]   DETECTION OF DISTRIBUTION HIGH IMPEDANCE FAULTS USING BURST NOISE SIGNALS NEAR 60 HZ [J].
AUCOIN, M ;
RUSSELL, BD .
IEEE TRANSACTIONS ON POWER DELIVERY, 1987, 2 (02) :342-348
[3]   A MICROPROCESSOR-BASED TECHNIQUE FOR DETECTION OF HIGH IMPEDANCE FAULTS [J].
BALSER, SJ ;
CLEMENTS, KA ;
LAWRENCE, DJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 1986, 1 (03) :252-258
[4]  
JOTA PRS, 1996, THESIS STATE U CAMPI
[5]   BEHAVIOR OF LOW-FREQUENCY SPECTRA DURING ARCING FAULT AND SWITCHING EVENTS [J].
RUSSELL, BD ;
CHINCHALI, RP ;
KIM, CJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (04) :1485-1492
[6]   A DIGITAL SIGNAL-PROCESSING ALGORITHM FOR DETECTING ARCING FAULTS ON POWER DISTRIBUTION FEEDERS [J].
RUSSELL, BD ;
CHINCHALI, RP .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (01) :132-140
[7]  
SILVA PR, 1994, PROCEEDINGS OF THE 1994 IEEE POWER ENGINEERING SOCIETY TRANSMISSION AND DISTRIBUTION CONFERENCE, P276, DOI 10.1109/TDC.1994.328392
[8]  
SILVA PR, 1995, 88 MIDWEST IEEE RIO, V1, P453
[9]  
SILVA PR, 1992, THESIS FEDERAL U MIN
[10]   DETECTING ARCING DOWNED-WIRES USING FAULT CURRENT FLICKER AND HALF-CYCLE ASYMMETRY [J].
SULTAN, AF ;
SWIFT, GW ;
FEDIRCHUK, DJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (01) :461-467