Flow distortions at the fan inlet of forced-draught air-cooled heat exchangers

被引:50
作者
Duvenhage, K [1 ]
Vermeulen, JA [1 ]
Meyer, CJ [1 ]
Kroger, DG [1 ]
机构
[1] UNIV STELLENBOSCH,DEPT MECH ENGN,STELLENBOSCH 7600,SOUTH AFRICA
关键词
air-cooled heat exchanger; forced-draught; axial fan; flow distortions; inlet shroud;
D O I
10.1016/1359-4311(95)00063-1
中图分类号
O414.1 [热力学];
学科分类号
摘要
The effect of inlet flow distortions on fan performance in forced-draught air-cooled heat exchangers (ACHEs) is investigated numerically and experimentally. By varying the distance between the ACHE fan platform and the ground level, significant changes in air volume dow rate are observed. Three different fan inlet shrouds are considered and recommendations towards designing and evaluating the performance of an ACHE are made. The effect of different lengths of a cylindrical fan inlet shroud, as well as the effect of cylindrical sections as part of a conical and a bell-mouth inlet shroud, is also investigated. The results show that a critical length for both the cylindrical inlet shroud and the cylindrical sections of the conical and bell-mouth inlet shrouds can be obtained for optimal fan performance. Copyright (C) 1996 Elsevier Science Ltd
引用
收藏
页码:741 / 752
页数:12
相关论文
共 22 条
[1]  
BRIGGS DE, 1963, CHEM ENG S SER, V41, P1
[2]  
DUTOIT CG, 1991, P 2 NAT S COMP FLUID, P24
[3]  
Holman J. P., 1989, Heat Transfer
[4]   FAN PERFORMANCE IN AIR-COOLED STEAM CONDENSERS [J].
KROGER, DG .
HEAT RECOVERY SYSTEMS & CHP, 1994, 14 (04) :391-399
[5]  
Launder B. E., 1974, Computer Methods in Applied Mechanics and Engineering, V3, P269, DOI 10.1016/0045-7825(74)90029-2
[6]  
Launder B.E., 1972, P NASA C FREE SHEAR
[7]  
Monroe R.C, 1979, COMBUSTION MAGAZINE, V50
[8]  
MOORE FK, 1977, CORNELL ENERGY REPOR
[9]  
Patankar S. V., 1980, NUMERICAL HEAT TRANS, pp. 88
[10]  
RADOSAVLJEVIC D, 1989, P INT COOL TOW C