Utilisation of plug-in electric vehicles for frequency regulation of multi-area thermal interconnected power systemInspec keywordsOther keywords

被引:28
作者
Gaur, Pushpa [1 ]
Bhowmik, Debashish [2 ]
Soren, Nirmala [1 ]
机构
[1] Natl Inst Technol Silchar, Dept Elect Engn, Silchar, Assam, India
[2] Tripura Inst Technol Narsingarh, Dept Elect Engn, Agartala, Tripura, India
关键词
three-term control; robust control; thermal power stations; power system interconnection; frequency control; power generation control; optimisation; electric vehicles; plug-in electric vehicles; frequency regulation; multiarea thermal interconnected power system; system frequency; aggregate model; multiarea thermal system; robust secondary control; control areas; wind-driven optimisation technique; controller gains; 2DOF-PID controller; nominal system condition; freedom proportional-integral-derivative controller; system conditions; system dynamics; nominal loading condition; integrated PEVs; system performance; random loading condition;
D O I
10.1049/iet-esi.2018.0028
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
080707 [能源环境工程]; 082001 [油气井工程];
摘要
The application of plug-in electric vehicles (PEVs) is assumed to be wide in power system in regulating the system frequency in the near future. This paper provides an aggregate model of an interconnected multi-area thermal system with the incorporation of PEVs for frequency control in each of the three areas. Two degree of freedom proportional-integral-derivative (2DOF-PID) controller has been utilised for robust secondary control in all the three control areas. An optimisation technique inspired by nature named as wind-driven optimisation (WDO) technique is employed to decide the optimal values of the controller gains. The effectiveness of WDO optimised 2DOF-PID controller is verified by performing various comparative analysis with conventional PID controller under nominal system condition and random loading condition. An analysis has also been carried out to evaluate the system performance with variation in state of the integrated PEVs. The impact of introducing PEVs in the system in frequency regulation has been vigorously studied under different system conditions such as nominal, random loading condition, and simultaneous perturbation in two and three areas to testify their advantages. The comparisons reveal that with the integration of PEVs in the system, the system dynamics gets enhanced to a large extent.
引用
收藏
页码:88 / 96
页数:9
相关论文
共 31 条
[1]
BFOA based design of PID controller for two area Load Frequency Control with nonlinearities [J].
Ali, E. S. ;
Abd-Elazim, S. M. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2013, 51 :224-231
[2]
Bacteria foraging optimization algorithm based load frequency controller for interconnected power system [J].
Ali, E. S. ;
Abd-Elazim, S. M. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2011, 33 (03) :633-638
[3]
[Anonymous], 1982, ELECT ENERGY SYSTEMS
[4]
[Anonymous], 2013, IEEE GRENOBLE POWERT
[5]
The Wind Driven Optimization Technique and its Application in Electromagnetics [J].
Bayraktar, Zikri ;
Komurcu, Muge ;
Bossard, Jeremy A. ;
Werner, Douglas H. .
IEEE TRANSACTIONS ON ANTENNAS AND PROPAGATION, 2013, 61 (05) :2745-2757
[6]
A simulation model for AGC studies of hydro-hydro systems [J].
Divya, KC ;
Rao, PSN .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2005, 27 (5-6) :335-342
[7]
OPTIMUM MEGAWATT-FREQUENCY CONTROL OF MULTIAREA ELECTRIC ENERGY SYSTEMS [J].
ELGERD, OI ;
FOSHA, CE .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1970, PA89 (04) :556-&
[8]
Model predictive control of plug-in hybrid electric vehicles for frequency regulation in a smart grid [J].
Elsisi, M. ;
Soliman, Mahmoud ;
Aboelela, Magdy A. S. ;
Mansour, W. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (16) :3974-3983
[9]
Load-frequency control of interconnected power system using emotional learning-based intelligent controller [J].
Farhangi, Reza ;
Boroushaki, Mehrdad ;
Hosseini, Seyed Hamid .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2012, 36 (01) :76-83
[10]
Gaur P, 2018, INT J RENEW ENERGY R, V8, P1580