Monitoring hydrofluorocarbon refrigerant leakage from air-conditioning systems in buildings

被引:9
作者
Cheong, KW [1 ]
Riffat, SB [1 ]
机构
[1] UNIV NOTTINGHAM, SCH ARCHITECTURE, BLDG TECHNOL GRP, NOTTINGHAM NG7 2RD, ENGLAND
关键词
D O I
10.1016/0306-2619(95)00027-5
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Hydrofluorocarbons (HFCs) are now widely used in refrigeration and air-conditioning systems. These systems lose refrigerants through leaks and during servicing. This paper discusses the possibility of determining the emission rate of HFCs in buildings by applying tracer-gas techniques. The measurement of the emission rate of an HFC refrigerant (R134a) using the concentration-decay technique was carried out in a single-zone chamber. The results were compared with measurements made using an SF6 tracer and the Pitot-tube traverse method.