Justification of Effective Reactive Power Reserves With Respect to a Particular Bus Using Linear Sensitivity

被引:43
作者
Choi, Y. H. [1 ]
Seo, S. [1 ]
Kang, S. [1 ]
Lee, B. [1 ]
机构
[1] Korea Univ, Dept Elect Engn, Seoul 136713, South Korea
关键词
Effective reactive power (Q) reserve (EQR); particular bus; reactive power reserve; sensitivity; voltage stability; IMPROVING VOLTAGE STABILITY; SYSTEM;
D O I
10.1109/TPWRS.2011.2151212
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
080906 [电磁信息功能材料与结构]; 082806 [农业信息与电气工程];
摘要
A constant reactive power (Q) reserve (CQR) is measured by the difference between the maximum reactive power generation and its current. However, all reactive power sources must not affect the entire power system when severe contingencies occur. Thus, generators must be evaluated as to whether or not they will have an impact on the maximum permissible loading of buses. This definition considers some generators to still have reactive power reserves when the system faces voltage collapse. This remaining reactive power reserve, although available, cannot be used in an arbitrary manner. This paper proposes the concept of an effective reactive power reserve and it is calculated on the basis of a sensitivity analysis. The computed reactive power reserve is analyzed using static and dynamic simulations in bulk power systems.
引用
收藏
页码:2118 / 2124
页数:7
相关论文
共 21 条
[1]
[Anonymous], 1994, Power System Voltage Stability
[2]
[Anonymous], 2001, IREP C ON JAP
[3]
Determination of power system coherent bus groups by novel sensitivity-based method for voltage stability assessment [J].
Aumuller, CA ;
Saha, TK .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2003, 18 (03) :1157-1164
[4]
Online voltage stability monitoring using var reserves [J].
Bao, LX ;
Huang, ZY ;
Xu, WS .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2003, 18 (04) :1461-1469
[5]
Corsi S., 2007, CESI ITALY FEASIBILI
[6]
Improving voltage stability by reactive power reserve management [J].
Dong, F ;
Chowdhury, BH ;
Crow, ML ;
Acar, L .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2005, 20 (01) :338-345
[7]
A study on determination of interface flow limits in the KEPCO system using modified continuation power flow (MCPF) [J].
Lee, B ;
Song, H ;
Kwon, SH ;
Jang, G ;
Kim, JH ;
Ajjarapu, V .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2002, 17 (03) :557-564
[8]
Leonardi B., P 2008 IEEE POW EN S, P1
[9]
A fast voltage security assessment method using adaptive bounding [J].
Liu, H ;
Bose, A ;
Venkatasubramanian, V .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2000, 15 (03) :1137-1141
[10]
MVAR management on the pre-dispatch problem for improving voltage stability margin [J].
Menezes, TV ;
da Silva, LCP ;
Affonso, CM ;
da Costa, VF .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2004, 151 (06) :665-672