Performance of a 500 kWP grid connected photovoltaic system at Mae Hong Son Province, Thailand

被引:75
作者
Chokmaviroj, S
Wattanapong, R
Suchart, Y
机构
[1] Elect Generating Author Thailand, Commun Syst Maintenance Sect 1, No Reg Operat Div, Commun Syst Maintenance Dept, Phitsanulok 65000, Thailand
[2] Naresuan Univ, Sch Renewable Energy Technol, Phitsanulok 65000, Thailand
[3] Naresuan Univ, Fac Engn, Dept Elect & Comp Engn, Phitsanulok 65000, Thailand
关键词
solar power system; performance; grid connected system;
D O I
10.1016/j.renene.2005.03.004
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This paper summarises the first eight months of monitoring of the PHA BONG photovoltaic generation project, a 500 kW(p) photovoltaic pilot plant, in Mae Hong Son province, Thailand. The local grid in this remote area in the North West of Thailand is very limited in its capacity and cannot be enlarged. It has been in operation since 20 March 2004 by feeding into 400 VAC, 22 kV medium voltage grid. The system consist of a photovoltaic array 1680 modules (140 strings, 12 modules/string; 300 W/module), power conditioning units and battery converter system. During the first eight months of this system's operation, the PV system generated about 383,274 kWh. The average of generating electricity production per day was 1695.9 kWh. It ranged from 1452.3 to 2042.3 kWh. The efficiency of the PV array system ranged from 9 to 12%. The efficiency of the power conditioning units (PCU) is in the range from 92 to 98%. The final yield (YF) ranged from 2.91 to 3.98 h/d and the performance ratio (PR) range from 0.7 to 0.9. (c) 2005 Elsevier Ltd. All rights reserved.
引用
收藏
页码:19 / 28
页数:10
相关论文
共 7 条
[1]  
CHOKMAVIROJ S, 2002, P INT C VILL POW REN, P102
[2]  
IEC, IEC standard 61724. 1998.
[3]  
JAHN U, 2000, 16 EUR PHOT SOL EN C
[4]   Performance of a grid connected small PV system in Poland [J].
Pietruszko, SM ;
Gradzki, M .
APPLIED ENERGY, 2003, 74 (1-2) :177-184
[5]  
RAKWICHIAN W, 2003, 2 EUR PV HYBR MIN GR
[6]  
*RES DEV OFF, EL GEN AUTH THAIL, P8
[7]  
ULRIKE J, 2000, T201 IEA PVPS