Developing novel 5th generation district energy networks

被引:122
作者
Revesz, Akos [1 ]
Jones, Phil [2 ]
Dunham, Chris [3 ]
Davies, Gareth [1 ]
Marques, Catarina [1 ]
Matabuena, Rodrigo [4 ]
Scott, Jim [5 ]
Maidment, Graeme [1 ]
机构
[1] London South Bank Univ, London, England
[2] Bldg Energy Solut, London, England
[3] Carbon Descent, London, England
[4] London Borough Islington, London, England
[5] Grid Edge, Birmingham, W Midlands, England
基金
英国工程与自然科学研究理事会; “创新英国”项目;
关键词
Thermal; Power; Mobility; Smart; Integrated; Networks; HEAT-RECOVERY; USERS; MANAGEMENT; SYSTEMS; GRIDS;
D O I
10.1016/j.energy.2020.117389
中图分类号
O414.1 [热力学];
学科分类号
070201 [理论物理];
摘要
Integrated smartly controlled energy networks have the potential to deliver significant reductions in carbon emissions, improve air quality and reduce energy costs for end-users across the world. This paper introduces a novel methodology for the development of integrated thermal, power and mobility 5th generation (5G) smart energy networks. The proposed 5G concept builds on state of the art by connecting flexible electricity demands such as heat pumps, and electric vehicles to intermittent, renewable and secondary energy sources and storage using artificial intelligence to facilitate optimal control and to maximise revenue and carbon savings. The proposed innovative method is being applied in central London through the development of two independent 5G smart energy schemes. The proposed schemes will incorporate a range of different renewables and secondary energy sources, for example, waste heat from local data centres and the London Underground that will supply a large proportion of the energy demand of the overall district network capacity. Both networks will operate at close to ambient temperature, approximately 15-25 degrees C as a so-called 'ambient loop' system, with individual heat pumps for each end-user or building connected to the network. The system also integrates thermal and electrical storage to create additional flexibility for the network and smart control for demand-side management. A smart management system flexibly controls individual assets such as heat pumps and electric vehicles in response to price signals reflecting the intermittency of renewable energy sources on the electricity grid. The ambient district thermal loop will distribute low carbon energy to a range of end users. Results presented in this paper provide an understanding of capital costs associated with integrated smart energy systems and the relative performance of individual technologies in a complex system using a techno-economic modelling approach. Overall, this paper demonstrates that the implementation of the 5G concept results in lower energy costs to consumers while at the same time transforming a large existing urban area to a near zero-carbon energy system in terms of heating, cooling, electricity and transport. (C) 2020 Elsevier Ltd. All rights reserved.
引用
收藏
页数:15
相关论文
共 43 条
[1]
Analytic versus solver-based calculated daily operations of district energy plants [J].
Andersen, Anders N. ;
Ostergaard, Poul Alberg .
ENERGY, 2019, 175 :333-344
[2]
Feasibility analysis of grid-connected and islanded operation of a solar PV microgrid system: A case study of Iraq [J].
Aziz, Ali Saleh ;
Tajuddin, Mohammad Faridun Naim ;
Adzman, Mohd Rafi ;
Mohammed, Mohd Fayzul ;
Ramli, Makbul A. M. .
ENERGY, 2020, 191
[4]
BBC, 2020, BBC News
[5]
BEIS, 2018, Clean Growth-Transforming Heating-Overview of Current Evidence, P136
[6]
BEIS, 2018, 2018 UK GREENH GAS E
[7]
BRGM, D2GRIDS DEPL NEW 5 G
[8]
5th generation district heating and cooling systems: A review of existing cases in Europe [J].
Buffa, Simone ;
Cozzini, Marco ;
D'Antoni, Matteo ;
Baratieri, Marco ;
Fedrizzi, Roberto .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2019, 104 :504-522
[9]
Economic analysis and optimal energy management models for microgrid systems: A case study in Taiwan [J].
Chen, Yen-Haw ;
Lu, Su-Ying ;
Chang, Yung-Ruei ;
Lee, Ta-Tung ;
Hu, Ming-Che .
APPLIED ENERGY, 2013, 103 :145-154
[10]
Using data centres for combined heating and cooling: An investigation for London [J].
Davies, G. F. ;
Maidment, G. G. ;
Tozer, R. M. .
APPLIED THERMAL ENGINEERING, 2016, 94 :296-304