Experimental study of a heat pump system with flash-tank coupled with scroll compressor

被引:132
作者
Ma Guo-Yuan [1 ]
Zhao Hui-Xia [1 ]
机构
[1] Beijing Univ Technol, Coll Environm & Energy Engn, Beijing 100022, Peoples R China
关键词
heat pump; economizer; scroll compressor; flash-tank;
D O I
10.1016/j.enbuild.2007.05.003
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A heat pump system with a flash-tank coupled with a scroll compressor is compared with a system with a sub-cooler. The heat pump performance was measured experimentally. The heating capacity of the prototype decreased as the evaporation temperature decreased, but the decrease was much slower than that of a conventional air-source heat pump. The power input varied slightly with the evaporation temperature. The heat pump system with a flash-tank is more efficient than the system with a sub-cooler at low ambient temperatures, so it will be very useful as a small capacity air-source heat pump. (C) 2007 Published by Elsevier B.V.