Copper and silver ions more effective against legionellae than against mycobacteria in a hospital warm water system

被引:77
作者
Kusnetsov, J
Iivanainen, E
Elomaa, N
Zacheus, O
Martikainen, PJ
机构
[1] Natl Publ Hlth Inst, Lab Environm Microbiol, FIN-70701 Kuopio, Finland
[2] Cent Hosp Vaasa, FIN-65130 Vaasa, Finland
[3] Univ Kuopio, Dept Environm Sci, FIN-70211 Kuopio, Finland
关键词
copper; silver; ionisation; prevention; control; legionella; mycobacteria;
D O I
10.1016/S0043-1354(01)00124-5
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
We studied the influence of electrolytically released copper and silver ions on the microbiological quality in a warm water system of a hospital. The concentration of nontuberculous mycobacteria was followed for three, and that of legionellae and other heterotrophic bacteria in the water for four years. The highest concentrations of copper and silver ions were 220 and 68 mug/l, respectively. Silver ion concentration of about 3 mug/l was sufficient to control the growth of legionellae in circulating warm water. The results showed that it is more difficult to eradicate legionellae from taps and showers: these points were colonized by a small number of legionellae after the metal ion concentrations were increased in the circulating water. A regular use of water eradicated legionellae from the shower. One tap was still used irregularly, and this may be a reason why it still contained small concentrations of legionellae also in the last years of the study. Mycobacteria were occasionally isolated from the circulating water and repeatedly from the shower, even when the metal concentrations were high. To control legionella bacteria in warm water systems, silver concentrations of only 3 mug/l are needed if all taps and showers of the system are regularly used. Such low copper and silver concentrations, however, are not efficient against nontuberculous mycobacteria or other heterotrophic bacteria. (C) 2001 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:4217 / 4225
页数:9
相关论文
共 45 条
[1]  
[Anonymous], 1998, 11731 ISO
[2]  
BAILEY RK, 1970, AM REV RESPIR DIS, V101, P430
[3]   COMPARATIVE MYCOBACTERICIDAL EFFICACY OF CHEMICAL DISINFECTANTS IN SUSPENSION AND CARRIER TESTS [J].
BEST, M ;
SATTAR, SA ;
SPRINGTHORPE, VS ;
KENNEDY, ME .
APPLIED AND ENVIRONMENTAL MICROBIOLOGY, 1988, 54 (11) :2856-2858
[4]   ISOLATION OF LEGIONELLA SPP FROM ENVIRONMENTAL WATER SAMPLES BY LOW-PH TREATMENT AND USE OF A SELECTIVE MEDIUM [J].
BOPP, CA ;
SUMNER, JW ;
MORRIS, GK ;
WELLS, JG .
JOURNAL OF CLINICAL MICROBIOLOGY, 1981, 13 (04) :714-719
[5]   ISOLATION OF MYCOBACTERIUM-XENOPEI FROM WATER TAPS [J].
BULLIN, CH ;
TANNER, EI ;
COLLINS, CH .
JOURNAL OF HYGIENE-CAMBRIDGE, 1970, 68 (01) :97-&
[6]  
CARSON LA, 1978, APPL ENVIRON MICROB, V36, P839, DOI 10.1128/AEM.36.6.839-846.1978
[7]   EFFICACY OF A COMBINED SYSTEM OF COPPER AND SILVER AND FREE CHLORINE FOR INACTIVATION OF NAEGLERIA-FOWLERI AMEBAS IN WATER [J].
CASSELLS, JM ;
YAHYA, MT ;
GERBA, CP ;
ROSE, JB .
WATER SCIENCE AND TECHNOLOGY, 1995, 31 (5-6) :119-122
[8]   OUTBREAK OF LEGIONNAIRES-DISEASE AT UNIVERSITY-HOSPITAL, NOTTINGHAM - EPIDEMIOLOGY, MICROBIOLOGY AND CONTROL [J].
COLVILLE, A ;
CROWLEY, J ;
DEARDEN, D ;
SLACK, RCB ;
LEE, JV .
EPIDEMIOLOGY AND INFECTION, 1993, 110 (01) :105-116
[9]   A NOTE ON THE TEMPERATURE TOLERANCE OF LEGIONELLA [J].
DENNIS, PJ ;
GREEN, D ;
JONES, BPC .
JOURNAL OF APPLIED BACTERIOLOGY, 1984, 56 (02) :349-350
[10]   IMPROVED SEMISELECTIVE MEDIUM FOR ISOLATION OF LEGIONELLA-PNEUMOPHILA FROM CONTAMINATED CLINICAL AND ENVIRONMENTAL SPECIMENS [J].
EDELSTEIN, PH .
JOURNAL OF CLINICAL MICROBIOLOGY, 1981, 14 (03) :298-303