Transmission line conductor temperature impact on state estimation accuracy

被引:80
作者
Bockarjova, Marija [1 ]
Andersson, Goeran [1 ]
机构
[1] ETH, Power Syst Lab, CH-8092 Zurich, Switzerland
来源
2007 IEEE LAUSANNE POWERTECH, VOLS 1-5 | 2007年
关键词
measurement errors; power system state estimation; transmission lines; power transmission meteorological factors;
D O I
10.1109/PCT.2007.4538401
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 [动力工程及工程热物理]; 0820 [石油与天然气工程];
摘要
State estimation has become a tool of vital importance in modern control centers. If the accuracy of the state estimation could be increased this will mean that a more reliable representation of the power system is obtained and the operation and control functions can make better decisions. This paper studies the influence of changes of the transmission lines resistance due to temperature on state estimation performance. The possibility to account for this effect in state estimation is shown by the use of Line Heat Balance equation and weather data.
引用
收藏
页码:701 / 706
页数:6
相关论文
共 14 条
[1]
Abur A., 2004, Power System State Estimation: Theory and Implementation
[2]
[Anonymous], 2000, MATH HDB SCI ENG DEF
[3]
[Anonymous], 1993, 7381993 IEEE
[4]
CLEMENTS K, 1974, POWER APPARATUS JUL
[5]
HOUSE HE, 1958, IEEE T POWER APP FEB, P1169
[6]
*IEEE, IEEE SYST DESCR
[7]
*KEMA, 2006, E INT PHAS PROJ
[8]
LEWIS WA, 1958, IEEE T POWER APP FEB, P1189
[9]
Effects of alternating and direct current, power frequency, temperature, and tension on the electrical parameters of ACSR conductors [J].
Morgan, VT .
IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (03) :859-866
[10]
POWER SYSTEM STATIC-STATE ESTIMATION .1. EXACT MODEL [J].
SCHWEPPE, FC ;
WILDES, J .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1970, PA89 (01) :120-&