Performance of cooling tower in south of Tunisia

被引:17
作者
Kairouani, L [1 ]
Hassairi, M [1 ]
Tarek, Z [1 ]
机构
[1] Ecole Natl Ingn Tunis, Unite Rech Mecan Energet, Belvedere 1002, Tunisia
关键词
cooling tower; geothermal water; mathematical model; water losses;
D O I
10.1016/j.buildenv.2003.08.017
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper presents a mathematical model for the numerical prediction of the performance of crossflow cooling towers. The mathematical model is based on the heat and mass transfer equations. The leading parameters are the Lewis number Le, the number of transfer units U, the percentage of water evaporation, the water losses and the tower efficiency. This model is used to predict the thermal behavior of six cooling towers located in the South of Tunisia. These towers are employed to decrease the temperature of geothermal water from 65degreesC to 34degreesC using a crossflow air. The total flow rate of water is 900 kg s(-1) and that of dry air is 1840 kg s(-1). Several experimental data have been collected on site, in order to adopt the mathematical model. The model has been used to predict the performance of cooling towers in terms of the meteorological conditions prevailing in the South of Tunisia. An optimal water loss quantity has been determined. On an annual basis, the actual water losses by evaporation represent 4% of the total water flow rate which correspond to 10(6) m(3) year(-1). This represents the annual consumption of 20 000 inhabitants. (C) 2003 Elsevier Ltd. All rights reserved.
引用
收藏
页码:351 / 355
页数:5
相关论文
共 14 条
[1]  
*BRIT STAND I, 1988, 4485 BS
[2]   Application of a general non-dimensional mathematical model to cooling towers [J].
Halasz, B .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 1999, 38 (01) :75-88
[3]   A general mathematical model of evaporative cooling devices [J].
Halasz, B .
REVUE GENERALE DE THERMIQUE, 1998, 37 (04) :245-255
[4]  
HASSAIRI M, 2001, 10 J INT THERM EPT M
[5]   Numerical study of the thermal-hydraulic performance of evaporative natural draft cooling towers [J].
Hawlader, MNA ;
Liu, BM .
APPLIED THERMAL ENGINEERING, 2002, 22 (01) :41-59
[6]  
KAIROUANI L, 2002, NUMERICAL MODELISATI
[7]   Evaluation of the amount of the atmospheric humidity condensed naturally [J].
Kounouhewa, B ;
Awanou, CN .
RENEWABLE ENERGY, 1999, 18 (02) :223-247
[8]  
KUNGXIONG T, 2003, BUILD ENVIRON, V38, P91
[9]  
LERECKNAGEL, 1986, MANUEL PRATIQUE GENI
[10]   NUMERICAL MODELING OF WET COOLING-TOWERS .1. MATHEMATICAL AND PHYSICAL MODELS [J].
MAJUMDAR, AK ;
SINGHAL, AK ;
SPALDING, DB .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1983, 105 (04) :728-735