An Explanation of Oscillations Due to Wind Power Plants Weak Grid Interconnection

被引:103
作者
Fan, Lingling [1 ]
Miao, Zhixin [1 ]
机构
[1] Univ S Florida, Dept Elect Engn, Tampa, FL 33420 USA
关键词
Voltage oscillations; weak grids; wind power plants;
D O I
10.1109/TSTE.2017.2713980
中图分类号
X [环境科学、安全科学];
学科分类号
083001 [环境科学];
摘要
An existing wind power plant at ERCOT experienced poorly damped and undamped voltage oscillations under weak grid conditions. The oscillations became worse during high power outputs. This letter aims to find the root cause of such oscillations. Our research provides a linearized system model by combining the vector control of wind power plants and the weak grid interconnection. Using thismodel, this letter succeeds in explaining that the weak grid condition introduces a zero in right half plane for the open-loop system, which can lead to poorly damped or undamped oscillations.