Partial discharge monitoring for power transformers using UHF sensors - part 2: Field experience

被引:175
作者
Judd, MD [1 ]
Yang, L
Hunter, IBB
机构
[1] Univ Strathclyde, Inst Energy & Environm, Glasgow G1 1XQ, Lanark, Scotland
[2] Glasgow Caledonian Univ, High Voltage Insulat Diagnost Grp, Glasgow G4 0BA, Lanark, Scotland
基金
英国工程与自然科学研究理事会;
关键词
power transformers; partial discharge (PD) testing; UHF sensors; UHFPD monitoring; portable monitoring;
D O I
10.1109/MEI.2005.1437603
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 [电气工程]; 0809 [电子科学与技术];
摘要
Field trials were carried out on five power transformers ranging in size from 18 to 1000 MVA and in voltage from 25 to 400 kV. The tests helped to define what will be required of a portable UHF monitor for power transformers. Results highlight the capabilities of the UHF technique as well as some of the challenges to be overcome and should be helpful to anyone intending to use UHF sensors to locate PD or arcing in transformers.
引用
收藏
页码:5 / 13
页数:9
相关论文
共 13 条
[1]
Transfer function-based partial discharge localization in power transformers: A feasibility study [J].
Akbari, A ;
Werle, P ;
Borsi, H ;
Gockenbach, E .
IEEE ELECTRICAL INSULATION MAGAZINE, 2002, 18 (05) :22-32
[2]
BENNOCH CJ, 2003, P 13 INT S HIGH VOLT
[3]
A review of faults detectable by gas-in-oil analysis in transformers [J].
Duval, M .
IEEE ELECTRICAL INSULATION MAGAZINE, 2002, 18 (03) :8-17
[4]
Judd MD, 2005, IEEE ELECTR INSUL M, V21, P5, DOI [10.1109/MEI.2005.1412214, 10.1109/MEI.2005.1437603]
[5]
Power transformer monitoring using UHF sensors: site trials [J].
Judd, MD ;
Cleary, GP ;
Bennoch, CJ ;
Pearson, JS ;
Breckenridge, T .
CONFERENCE RECORD OF THE 2002 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2002, :145-149
[6]
Dielectric windows for UHF partial discharge detection [J].
Judd, MD ;
Farish, O ;
Pearson, JS ;
Hampton, BF .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2001, 8 (06) :953-958
[7]
JUDD MD, 2003, P 13 INT S HIGH VOLT
[8]
Recognition of discharge sources using UHFPD signatures [J].
Raja, K ;
Devaux, F ;
Lelaidier, S .
IEEE ELECTRICAL INSULATION MAGAZINE, 2002, 18 (05) :8-14
[9]
Comparative investigations on UHF and acoustic PD detection sensitivity in transformers [J].
Raja, K ;
Floribert, T .
CONFERENCE RECORD OF THE 2002 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2002, :150-153
[10]
Location of partial discharges in power transformers using computer-aided acoustic techniques [J].
Tang, L ;
Wu, ZR ;
Li, HZ ;
Nie, DX .
CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING-REVUE CANADIENNE DE GENIE ELECTRIQUE ET INFORMATIQUE, 1996, 21 (02) :67-71