Grid-friendly connecting of constant-speed wind turbines using external resistors

被引:25
作者
Thiringer, T [1 ]
机构
[1] Chalmers Univ Technol, Dept Elect Power Engn, S-41296 Gothenburg, Sweden
关键词
capacitors; power quality; resistors; wind energy;
D O I
10.1109/TEC.2002.805221
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this paper, an alternative method of connecting fixed-speed wind turbines, with active pitch mechanisms or variable-slip generators, is proposed and evaluated. Instead of using the conventional soft starter, external resistors are used. The method was evaluated via laboratory tests on a 15-kW machine and theoretically on a 1-MW wind turbine. The proposed method causes smaller grid power quality impact, especially on inductive grids, compared with soft starters. This means that it will be possible to install. constant-speed wind. turbines to weaker grids using this method.
引用
收藏
页码:537 / 542
页数:6
相关论文
共 8 条
[1]  
[Anonymous], 1984, TRANSIENT PHENOMENA
[2]  
GERDES G, 1997, P EUR WIND EN C DUBL, P716
[3]  
International Electrotechnical Commission, 1998, 6140021 IEC
[4]  
Kron A. W., 1969, Elektrotechnische Zeitschrift ETZ A, V90, P200
[5]  
LARSSON A, 1999, P 15 INT C EL DIST N
[6]  
Lemstrom B, 1999, P EUR WIND EN C NIC, P747
[7]   Power quality measurements performed on a low-voltage grid equipped with two wind turbines [J].
Thiringer, T .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1996, 11 (03) :601-606
[8]  
1999, CONNECTION SMALLER P