Experimental Study of PCM Inclusion in Different Building Envelopes

被引:64
作者
Castellon, C. [1 ]
Castell, A. [1 ]
Medrano, M. [1 ]
Martorell, I. [1 ]
Cabeza, L. F. [1 ]
机构
[1] Univ Lleida, GREA Innovacio Concurrent, Lleida 25001, Spain
来源
JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME | 2009年 / 131卷 / 04期
关键词
brick; building management systems; concrete; heat pumps; HVAC; phase change materials; power conversion; THERMAL-ENERGY STORAGE; PHASE-CHANGE; SIMULATION;
D O I
10.1115/1.3197843
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
080707 [能源环境工程]; 082001 [油气井工程];
摘要
The main objective of this paper is to demonstrate experimentally that it is possible to improve the thermal comfort and reduce the energy consumption of a building without substantial increase in the weight of the construction materials with the inclusion of phase change materials (PCM). PCM are a suitable and promising technology for this application. This paper presents an experimental setup to test PCM with various typical insulation and construction materials in real conditions in Puigverd de Lleida (Lleida, Spain). Nine small house-sized cubicles were constructed: two with concrete, five with conventional brick, and two with alveolar brick. PCM was added in one cubicle of each typology. For each type of construction specific experiments were done. In all cubicles, free-floating temperature experiments were performed to determine the benefits of using PCM. A Trombe wall was added in both concrete cubicles and its influence was investigated. All brick cubicles were equipped with domestic heat pumps as Heating, Ventilation, and Air Conditioning (HVAC) system; therefore, the energy consumption was registered, providing real information about the energy savings. Results were very good for the concrete cubicles, since temperature oscillation were reduced by up to 4 degrees C through the use of PCM and also peak temperatures in the PCM cubicle were shifted in later hours. In the brick cubicles, the energy consumption of the HVAC system in summer was reduced by using PCM for set points higher than 20 degrees C. During winter an insulation effect of the PCM is observed, keeping the temperatures of the cubicles warmer, especially during the cold hours of the day.
引用
收藏
页码:0410061 / 0410066
页数:6
相关论文
共 19 条
[1]
Experimental investigation and computer simulation of thermal behaviour of wallboards containing a phase change material [J].
Ahmad, M ;
Bontemps, A ;
Sallée, H ;
Quenard, D .
ENERGY AND BUILDINGS, 2006, 38 (04) :357-366
[2]
Thermal analysis of a building brick containing phase change material [J].
Alawadhi, Esam M. .
ENERGY AND BUILDINGS, 2008, 40 (03) :351-357
[3]
Use of microencapsulated PCM in concrete walls for energy savings [J].
Cabeza, Luisa F. ;
Castellon, Cecilia ;
Nogues, Miquel ;
Medrano, Marc ;
Leppers, Ron ;
Zubillaga, Oihana .
ENERGY AND BUILDINGS, 2007, 39 (02) :113-119
[4]
Numerical and experimental analyses of PCM containing sandwich panels for prefabricated walls [J].
Carbonari, A ;
De Grassi, M ;
Di Perna, C ;
Principi, P .
ENERGY AND BUILDINGS, 2006, 38 (05) :472-483
[5]
CASTELL A, 2009, THESIS U LLEIDA LLEI
[6]
CASTELLON C, 2008, THESIS U LLEIDA LLEI
[7]
Dincer I., 2002, Thermal energy storage: systems and applications
[8]
HADORN J., 2005, THERMAL ENERGY STORA
[9]
An approach to the simulation of PCMs in building applications using TRNSYS [J].
Ibáñez, M ;
Lázaro, A ;
Zalba, B ;
Cabeza, LF .
APPLIED THERMAL ENGINEERING, 2005, 25 (11-12) :1796-1807
[10]
A review on energy conservation in building applications with thermal storage by latent heat using phase change materials [J].
Khudhair, AM ;
Farid, MM .
ENERGY CONVERSION AND MANAGEMENT, 2004, 45 (02) :263-275