Enabling wind farm to be black-start source by energy storage

被引:10
作者
Liu, Weipeng [1 ]
Liu, Yutian [1 ]
机构
[1] Shandong Univ, Key Lab Power Syst Intelligent Dispatch & Control, Minist Educ, Jinan, Shandong, Peoples R China
来源
JOURNAL OF ENGINEERING-JOE | 2019年 / 18期
关键词
probability; wind power plants; frequency control; energy storage; synchronous generators; power generation economics; investment; power system control; power system reliability; energy storage system sizing method; black-start source; virtual synchronous generator; frequency regulation capability; wind farm; wind farm start up; kernel density estimation; probability distribution characteristics; minimum investment cost; POWER; SYSTEM;
D O I
10.1049/joe.2018.9302
中图分类号
T [工业技术];
学科分类号
120111 [工业工程];
摘要
An energy storage system (ESS) sizing method is proposed to enable wind farm (WF) to be a black-start (BS) source. This method handles three challenges: firstly, ESS has enough power to help WF start up. Secondly, the WF together with ESS is modelled as a virtual synchronous generator (VSG), and its frequency regulation capability is considered when sizing ESS. Thirdly, the power and capacity of ESS are determined so that VSG can deliver the required power during black-start. Instead of using wind speed probability distribution, kernel density estimation is used in this paper to directly estimate the probability distribution characteristics of ESS sizing. Simulation results show that with minimum investment cost on ESS, WF is able to be BS source.
引用
收藏
页码:5138 / 5141
页数:4
相关论文
共 10 条
[1]
A new approach for optimal sizing of battery energy storage system for primary frequency control of islanded Microgrid [J].
Aghamohammadi, Mohammad Reza ;
Abdolahinia, Hajar .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2014, 54 :325-333
[2]
Energization of Wind Turbine Transformers With an Auxiliary Generator in a Large Offshore Wind Farm During Islanded Operation [J].
Arana, I. ;
Hernandez, A. ;
Thumm, G. ;
Holboell, J. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (04) :2792-2800
[3]
A probabilistic method for calculating the usefulness of a store with finite energy capacity for smoothing electricity generation from wind and solar power [J].
Barton, John P. ;
Infield, David G. .
JOURNAL OF POWER SOURCES, 2006, 162 (02) :943-948
[4]
Statistical analysis of wind power forecast error [J].
Bludszuweit, Hans ;
Antonio Dominguez-Navarro, Jose ;
Llombart, Andres .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2008, 23 (03) :983-991
[5]
Methodology for the economic optimisation of energy storage systems for frequency support in wind power plants [J].
Johnston, Lewis ;
Diaz-Gonzalez, Francisco ;
Gomis-Bellmunt, Oriol ;
Corchero-Garcia, Cristina ;
Cruz-Zambrano, Miguel .
APPLIED ENERGY, 2015, 137 :660-669
[6]
Power system restoration: a literature review from 2006 to 2016 [J].
Liu, Yutian ;
Fan, Rui ;
Terzija, Vladimir .
JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, 2016, 4 (03) :332-341
[7]
Optimal sizing and control strategy of isolated grid with wind power and energy storage system [J].
Luo, Yi ;
Shi, Lin ;
Tu, Guangyu .
ENERGY CONVERSION AND MANAGEMENT, 2014, 80 :407-415
[8]
INDUCTION MACHINE MODELING FOR ELECTROMAGNETIC TRANSIENT PROGRAM [J].
ROGERS, GJ ;
SHIRMOHAMMADI, D .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1987, 2 (04) :622-628
[9]
Vaca SM, 2016, INT CONF RENEW ENERG, P325, DOI 10.1109/ICRERA.2016.7884560
[10]
Wei T., 2015, TENCON 2015, P1