Reinforced Control and Operation of DFIG-Based Wind-Power-Generation System Under Unbalanced Grid Voltage Conditions

被引:104
作者
Hu, Jiabing [1 ]
He, Yikang [1 ]
机构
[1] Zhejiang Univ, Coll Elect Engn, Hangzhou 310027, Zhejiang, Peoples R China
基金
中国国家自然科学基金;
关键词
Converter; doubly fed induction generator (DFIG); proportional plus resonant (P-R) controller; unbalance; wind power; FED INDUCTION GENERATOR; TURBINES; ERROR;
D O I
10.1109/TEC.2008.2001434
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper proposes an enhanced control and operation of a doubly fed induction generator (DFIG) based wind power generation system under unbalanced grid voltage conditions. System behaviors of grid-side and rotor-side converters (GSCs and RSCs) are described. The RSC is controlled to eliminate the electromagnetic torque oscillation at double the grid frequency. Meanwhile, three selective control targets for the GSC, i.e., reducing the pulsations in the total active or reactive power, or unbalanced current outputs from the overall system, are identified and analyzed during voltage imbalance. A new current-control scheme is presented for the GSC and RSC without involving the decomposing of positive and negative sequence currents. The controller consists of a proportional (P) regulator and a resonant (R) one tuned at the grid frequency, which is implemented in the stator stationary reference frame. Finally, simulation studies are carried out on a 1.5-MW wind-turbine-driven DFIG system. The validity of the presented current controller and the feasibility of the proposed control targets are all confirmed by the simulated results.
引用
收藏
页码:905 / 915
页数:11
相关论文
共 20 条
[1]  
[Anonymous], 2002, IEEE WORKSH WIND POW
[2]  
[Anonymous], P IEEE IND APPL C
[3]  
BREKKEN T, 2005, EUR C POW EL APPL MI
[4]  
BREKKEN T, P PESC 2003, V2, P760
[5]  
CHOMAT M, P POW EL MACH DRIV 2, P329
[6]  
CODD I, 2003, 4 INT WORKSH LARG SC
[7]   Statcom controls for operation with unbalanced voltages [J].
Hochgraf, C ;
Lasseter, RH .
IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (02) :538-544
[8]   Ridethrough of wind turbines with doubly-fed induction generator during a voltage dip [J].
Morren, J ;
de Haan, SWH .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2005, 20 (02) :435-441
[9]   Doubly fed induction generator systems for wind turbines [J].
Müller, S ;
Deicke, M ;
De Doncker, RW .
IEEE INDUSTRY APPLICATIONS MAGAZINE, 2002, 8 (03) :26-33
[10]  
*NAT GRID TRANSC, 2004, APP EXTR GRID COD CO