A techno-economic comparison of ground-coupled and air-coupled heat pump system for space cooling

被引:454
作者
Esen, Hikmet [1 ]
Inalli, Mustafa
Esen, Mehmet
机构
[1] Univ Firat, Fac Tech Educ, Dept Mech Educ, TR-23119 Elazig, Turkey
[2] Univ Firat, Fac Engn, Dept Mech Engn, TR-23119 Elazig, Turkey
关键词
heat pump; ground-coupled; air-coupled; techno-economic analysis; cooling; Turkey;
D O I
10.1016/j.buildenv.2006.04.007
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper reports a techno-economic comparison between a ground-coupled heat pump (GCHP) system and an air-coupled heat pump (ACHP) system. The systems connected to a test room in Firat University, Elazig (38.41 degrees N, 39.14 degrees E), Turkey, were designed and constructed for space cooling. The performances of the GCHP and the ACHP system were experimentally determined. The experimental results were obtained from June to September in cooling season of 2004. The average cooling performance coefficients (COPsys) of the GCHP system for horizontal ground heat exchanger (HGHE) in the different trenches, at 1 and 2 m depths, were obtained to be 3.85 and 4.26, respectively and the COPsys of the ACHP system was determined to be 3.17. The test results indicate that system parameters can have an important effect on performance, and that GCHP systems are economically preferable to ACHP systems for the purpose of space cooling. (c) 2006 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1955 / 1965
页数:11
相关论文
共 24 条
[1]  
Asan H, 1997, P 11 NATL HEAT SCI C, P369
[2]  
ASHRAE, 901 ASHRAE
[3]   Solar and ground source heat-pump system [J].
Bi, YH ;
Guo, TW ;
Zhang, L ;
Chen, LG .
APPLIED ENERGY, 2004, 78 (02) :231-245
[4]  
Coleman HW, 1999, EXPT UNCERTAINTY ANA, P4
[5]   A performance comparison between an air-source and a ground-source reversible heat pump [J].
De Swardt, CA ;
Meyer, JP .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2001, 25 (10) :899-910
[6]  
Elazig State Meteorological Station, 2004, REC WEATH DAT EL, P2004
[7]   Technoeconomic appraisal of a ground source heat pump system for a heating season in eastern Turkey [J].
Esen, H ;
Inalli, M ;
Esen, M .
ENERGY CONVERSION AND MANAGEMENT, 2006, 47 (9-10) :1281-1297
[8]  
ESEN H, 2002, TESIS U FIRAT ELAZIG
[9]   CO2 payback-time assessment of a regional-scale heating and cooling system using a ground source heat-pump in a high energy-consumption area in Tokyo [J].
Genchi, Y ;
Kikegawa, Y ;
Inaba, A .
APPLIED ENERGY, 2002, 71 (03) :147-160
[10]  
Healy PF, 1997, INT J ENERG RES, V21, P857, DOI 10.1002/(SICI)1099-114X(199708)21:10<857::AID-ER279>3.0.CO