Comprehensive exergy analysis of a ground-source heat pump system for both building heating and cooling modes

被引:127
作者
Bi, Yuehong [1 ,2 ]
Wang, Xinhong [2 ]
Liu, Yun [2 ]
Zhang, Hua [3 ]
Chen, Lingen [1 ]
机构
[1] Naval Univ Engn, Postgrad Sch, Wuhan 430033, Peoples R China
[2] Beijing Univ Technol, Inst Civil & Architectural Engn, Beijing 100124, Peoples R China
[3] Shanghai Univ Sci & Technol, Inst Refrigerat Technol, Shanghai 200093, Peoples R China
关键词
Ground-source heat pump; Building heating and cooling mode; Comprehensive exergy analysis; Exergy indexes; Energy saving; ENTROPY GENERATION MINIMIZATION; PERFORMANCE ASSESSMENT; THERMAL PERFORMANCE; SOLAR; GREENHOUSE; EXCHANGER; ENERGY; THERMODYNAMICS; OPTIMIZATION; SIMULATION;
D O I
10.1016/j.apenergy.2009.04.005
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents a comprehensive exergy analysis of three circuits and whole system of a ground-source heat pump (GSHP) for both building heating and cooling modes. The purpose is to search out the key potential energy saving components. The analytical formulae of exergy loss, exergy efficiency, exergy loss ratio, exergy loss coefficient and thermodynamic perfect degree are derived, respectively. The results show that these exergy indexes should be used integratively, and in the whole system the location of maximum exergy loss ratio is the compressor, while the location of minimum exergy efficiency and thermodynamic perfect degree is the ground heat exchanger, so that the compressor and the ground heat exchanger should be primarily improved. The results also indicate that the exergy loss of a GSHP system for building heating mode is bigger than that of cooling mode, and the exergy efficiency of a whole GSHP system is obviously lower than those of its components for both building heating and cooling modes. Therefore, a comprehensive exergy analysis of a GSHP should be paid more attention to. The results may provide guidelines for the design and optimization of GSHP systems. (C) 2009 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2560 / 2565
页数:6
相关论文
共 56 条
[1]   Modeling of a geothermal standing column well [J].
Abu-Nada, E. ;
Akash, B. ;
Al-Hinti, I. ;
Al-Sarkhi, A. ;
Nijmeh, S. ;
Ibrahim, A. ;
Shishan, A. .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2008, 32 (04) :306-317
[2]   A comparative study on exergetic assessment of two ground-source (geothermal) heat pump systems for residential applications [J].
Akpinar, Ebru Kavak ;
Hepbasli, Arif .
BUILDING AND ENVIRONMENT, 2007, 42 (05) :2004-2013
[3]  
[Anonymous], 1989, AVAILABILITY ANAL GU
[5]   Fundamentals of exergy analysis, entropy generation minimization, and the generation of flow architecture [J].
Bejan, A .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2002, 26 (07) :545-565
[6]  
Bejan A, 1995, Thermal design and optimization
[7]  
Berry R.S., 1999, Thermodynamic Optimization of Finite Time Processes
[8]   Heat source performance for solar-ground source heat pump [J].
Bi, Y ;
Chen, L ;
Wu, C .
JOURNAL OF THE ENERGY INSTITUTE, 2005, 78 (04) :185-189
[9]   Solar and ground source heat-pump system [J].
Bi, YH ;
Guo, TW ;
Zhang, L ;
Chen, LG .
APPLIED ENERGY, 2004, 78 (02) :231-245
[10]   Ground heat exchanger temperature distribution analysis and experimental verification [J].
Bi, YH ;
Chen, LG ;
Wu, C .
APPLIED THERMAL ENGINEERING, 2002, 22 (02) :183-189