Fungal colonization of air filters and insulation in a multi-story office building: Production of volatile organics

被引:48
作者
Ahearn, DG
Crow, SA
Simmons, RB
Price, DL
Mishra, SK
Pierson, DL
机构
[1] INTERFACE RES CORP,KENNESAW,GA 30144
[2] NASA,LYNDON B JOHNSON SPACE CTR,BIOMED OPERAT & RES BRANCH,HOUSTON,TX 77058
关键词
D O I
10.1007/s002849900259
中图分类号
Q93 [微生物学];
学科分类号
071005 ; 100705 ;
摘要
Secondary air filters in the air-handling units on four floors of a multi-story office building with a history of fungal colonization of insulation within the air distribution system were examined for the presence of growing fungi and production of volatile organic compounds. Fungal mycelium and conidia of Cladosporium and Penicillium spp. were observed on insulation from all floors and both sides of the air filters from one floor. Lower concentrations of volatile organics were released from air filter medium colonized with fungi as compared with noncolonized filter medium. However, the volatiles from the colonized filter medium included fungal metabolites such as acetone and a carbonyl sulfide-like compound that were not released from noncolonized filter medium. The growth of fungi in air distribution systems may affect the content of volatile organics in indoor air.
引用
收藏
页码:305 / 308
页数:4
相关论文
共 7 条
[1]   Fungal colonization of fiberglass insulation in the air distribution system of a multi-story office building: VOC production and possible relationship to a sick building syndrome [J].
Ahearn, DG ;
Crow, SA ;
Simmons, RB ;
Price, DL ;
Noble, JA ;
Mishra, SK ;
Pierson, DL .
JOURNAL OF INDUSTRIAL MICROBIOLOGY, 1996, 16 (05) :280-285
[2]  
BAYER CW, 1993, IAQ 93 ENV PEOPLE, P99
[3]   FUNGAL PRODUCTION OF VOLATILES DURING GROWTH ON FIBERGLASS [J].
EZEONU, IM ;
PRICE, DL ;
SIMMONS, RB ;
CROW, SA ;
AHEARN, DG .
APPLIED AND ENVIRONMENTAL MICROBIOLOGY, 1994, 60 (11) :4172-4173
[4]  
MISHRA SK, 1996, 96 GEN M AM SOC MICR, P387
[5]  
Samson RobertA., 1994, Health Implications of Fungi in Indoor Environments
[6]   FUNGAL COLONIZATION OF AIR FILTERS FOR USE IN HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC) SYSTEMS [J].
SIMMONS, RB ;
CROW, SA .
JOURNAL OF INDUSTRIAL MICROBIOLOGY, 1995, 14 (01) :41-45
[7]  
SIMMONS RB, 1997, IN PRESS AM IND HYG