Measurements and computations of contaminant's distribution in an office environment

被引:51
作者
Cheong, KWD [1 ]
Djunaedy, E [1 ]
Poh, TK [1 ]
Tham, KW [1 ]
Sekhar, SC [1 ]
Wong, NH [1 ]
Ullah, MB [1 ]
机构
[1] Natl Univ Singapore, Sch Design & Environm, Dept Bldg, Singapore 117566, Singapore
关键词
contaminant; CFD; measurement; computation; office; tracer-gas;
D O I
10.1016/S0360-1323(02)00031-8
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper investigates the dispersion of contaminants in an office environment using empirical and modeling techniques. The experiment was conducted in an environmental test facility with the mock-up of two typical office layouts. Layout 1 has two workstations located in the middle of the room and separated by a low-level partition, while Layout 2 has a low level-partition which separates the room into two halves with one workstation at each corner. The test facility, 6.6 m (L) x 3.7 m (W) x 2.6 m (H), is served by an air-conditioning and mechanical ventilation (ACMV) system which is capable of controlling the air temperature and airflow rates at the supply diffuser and extract grille. The contaminant's emission was generated by a constant injection of tracer gas, sulfur hexafluoride (SF6), via a 280 mm x 200 mm surface to represent the plane source. The concentration of contaminant in the chamber for both the layouts was measured and simulated using a gas analyzer and a computational fluid dynamic (CFD) program with the Re-Normalization Group k-r. model, respectively. In general, the predicted concentration of contaminant was in good correlation with the measured concentration. However, the predicted results were always marginally lower than the measured results. The contaminant's dispersion pattern was observed to be highly dependent on the velocity flow field. The layout of furniture influenced the airflow pattern and contaminant's distribution in the office. On the whole, Layout 1 was better than Layout 2 with a lower level of contaminant at the occupant's breathing zones. (C) 2002 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:135 / 145
页数:11
相关论文
共 12 条
[1]  
[Anonymous], 1990, GUL SERIE
[2]  
Awbi H.B., 1991, Ventilation of Buildings
[3]  
BLACK MS, 1999, INDOOR AIR 99, V2, P454
[4]  
BLACK MS, 1991, P IAQ 91 ATL AM SOC
[5]   Personal exposure in displacement ventilated rooms [J].
Brohus, H ;
Nielsen, PV .
INDOOR AIR-INTERNATIONAL JOURNAL OF INDOOR AIR QUALITY AND CLIMATE, 1996, 6 (03) :157-167
[6]   CHAMBER TESTING OF ORGANIC EMISSION FROM BUILDING AND FURNISHING MATERIALS [J].
COLOMBO, A ;
DEBORTOLI, M ;
PECCHIO, E ;
SCHAUENBURG, H ;
SCHLITT, H ;
VISSERS, H .
SCIENCE OF THE TOTAL ENVIRONMENT, 1990, 91 :237-249
[7]  
Etheridge D., 1996, Building Ventilation: Theory and Measurement
[8]  
JONES PJ, 1992, CFD BUILDING AIR FLO
[9]  
Molhave L., 1982, Environ. Int., V8, P117, DOI [DOI 10.1016/0160-4120(82)90019-8, 10.1016/0160-4120(82)90019-8]
[10]   OZONE PRODUCTION FROM PHOTOCOPYING MACHINES [J].
SELWAY, MD ;
ALLEN, RJ ;
WADDEN, RA .
AMERICAN INDUSTRIAL HYGIENE ASSOCIATION JOURNAL, 1980, 41 (06) :455-459