Study of epoxy/mica insulation deterioration in generator stator using ultra-wide band partial discharge testing technique

被引:15
作者
Chen, Xiaolin [1 ]
Cheng, Yonghong [1 ]
Yue, Bo [1 ]
Xie, Hengkun [1 ]
机构
[1] Xian Jiaotong Univ, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
关键词
generator; epoxy/mica insulation; deterioration; partial discharge; ultra-wide band;
D O I
10.1016/j.polymertesting.2006.05.011
中图分类号
TB3 [工程材料学];
学科分类号
0805 ; 080502 ;
摘要
The epoxy/mica insulation in a generator stator deteriorates under the conditions of thermal, electrical, vibrational and thermo-mechanical stresses when the generator is running. To assess the insulation aging status and to understand the deterioration process, an ultra-wide band partial discharge testing method was adopted in this study. A multi-stress accelerated aging equipment was established to imitate the actual service conditions. Obvious change in the waveforms of discharge pulses was observed when the epoxy/mica insulation was under accelerated aging condition in the laboratory. The test results indicated the formation and growth of voids in the insulation during the aging process. Furthermore, optical microscopy and SEM were used to examine the insulation. Delamination and cracks in the insulation were observed which accorded with the ultra-wide band partial discharge test results. (C) 2006 Elsevier Ltd. All rights reserved.
引用
收藏
页码:724 / 730
页数:7
相关论文
共 12 条
[1]   A PROBABILISTIC MODEL FOR EVALUATING THE REMAINING LIFE OF ELECTRICAL INSULATION IN ROTATING MACHINES [J].
ANDERS, GJ ;
ENDRENYI, J ;
FORD, GL ;
STONE, GC .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1990, 5 (04) :761-767
[2]  
Cheng YH, 2003, PROCEEDINGS OF THE 7TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1-3, P211
[3]   New practices for partial discharge detection and localization in large rotating machines [J].
Kheirmand, A ;
Leijon, M ;
Gubanski, SM .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2003, 10 (06) :1042-1052
[4]   ASSESSMENT OF DETERIORATION IN EPOXY MICA MACHINE INSULATION [J].
KIM, YJ ;
NELSON, JK .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1992, 27 (05) :1026-1039
[5]   THE ROLE OF MICROSCOPIC DEFECTS IN MULTISTRESS AGING OF MICACEOUS INSULATION [J].
KIMURA, K ;
KANEDA, Y .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1995, 2 (03) :426-432
[6]  
Kimura K., 1993, IEEE Electrical Insulation Magazine, V9, P13, DOI 10.1109/57.216783
[7]   THE ABILITY OF DIAGNOSTIC-TESTS TO ESTIMATE THE REMAINING LIFE OF STATOR INSULATION [J].
STONE, GC ;
SEDDING, HG ;
LLOYD, BA ;
GUPTA, BK .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1988, 3 (04) :833-841
[8]  
STONE GC, 1990, P IEEE INT S EL INS, P356
[9]   A novel physical model for partial discharge in narrow channels [J].
Wu, K ;
Suzuoki, Y ;
Mizutani, T ;
Xie, HK .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1999, 6 (02) :181-190
[10]  
Yue B, 2005, PROG NAT SCI, V15, P1035