Study of protection scheme for transmission line based on wavelet transient energy

被引:26
作者
Fan, Chunju
Li, K. K. [1 ]
Chan, W. L.
Yu, Weiyong
机构
[1] Hong Kong Polytech Univ, Dept Elect Engn, Kowloon, Hong Kong, Peoples R China
[2] Shanghai Jiao Tong Univ, Dept Elect Engn, Shanghai 200030, Peoples R China
关键词
power system protection; wavelet analysis; transient energy; modal transform;
D O I
10.1016/j.ijepes.2006.02.006
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Wavelet transient energy is proposed to be the criterion of protection for distinguishing internal or external fault on transmission line in this paper. The modal voltage and current are decomposed by Daubechies 4 wavelet in both time and frequency. The different decomposition coefficients on different scales reflecting different frequency information are used to calculate the transient characteristic of voltage and current. The transient characteristic is then utilized to obtain the transient energy of the fault that is employed to identify the fault position. Simulation results show that the proposed protection scheme based on transient energy is applicable and encouraging. It is independent of fault type, switching angle and generation mode; not influenced by recloser and lightning surge. Single-line ground fault with high fault resistance can also be detected correctly. The proposed protection scheme has good selectivity, reliability and sensitivity. (C) 2006 Elsevier Ltd. All rights reserved.
引用
收藏
页码:459 / 470
页数:12
相关论文
共 28 条
[1]  
Al-Rawi A, 1998, IEEE IMTC P, P1331, DOI 10.1109/IMTC.1998.676968
[2]   A new non-communication protection technique for transmission lines [J].
Bo, ZQ .
IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (04) :1073-1078
[3]   Identification and classification of faults on transmission lines using wavelet multiresolution analysis [J].
Chanda, D ;
Kishore, NK ;
Sinha, AK .
ELECTRIC POWER COMPONENTS AND SYSTEMS, 2004, 32 (04) :391-405
[4]   Study of wavelet-based ultra high speed directional transmission line protection [J].
Chen, W ;
Malik, OP ;
Yin, XG ;
Chen, DS ;
Zhang, Z .
IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (04) :1134-1139
[5]  
HAJJAR AA, 2002, IEEE CAN C EL COMP E, V1, P7
[6]   Modelling of a transmission tower for lightning-surge analysis [J].
Hara, T ;
Yamamoto, O .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1996, 143 (03) :283-289
[7]   Application of Morlet wavelets to supervise power system disturbances [J].
Huang, SJ ;
Hsieh, CT ;
Huang, CL .
IEEE TRANSACTIONS ON POWER DELIVERY, 1999, 14 (01) :235-243
[8]   High-impedance fault detection utilizing a Morlet wavelet transform approach [J].
Huang, SJ ;
Hsieh, CT .
IEEE TRANSACTIONS ON POWER DELIVERY, 1999, 14 (04) :1401-1410
[9]   A non-pilot phase selector based on superimposed components for protection of double circuit lines [J].
Jones, MS ;
Thomas, DWP ;
Christopoulos, C .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (04) :1439-1444
[10]   A practical fault location approach for double circuit transmission lines using single end data [J].
Kawady, T ;
Stenzel, J .
IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (04) :1166-1173