Frequency deviation of thermal power plants due to wind farms

被引:130
作者
Luo, Changling [1 ]
Ooi, Boon-Teck [1 ]
机构
[1] McGill Univ, Dept Elect & Comp Engn, Montreal, PQ H3A 2A7, Canada
基金
加拿大自然科学与工程研究理事会;
关键词
frequency fluctuation; governor; inertia; steam valve; transfer function; turbine; wind farms; wind power fluctuation;
D O I
10.1109/TEC.2006.874210
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents the results of a study on the frequency deviation of the utility grid due to wind power fluctuations. The deviation is estimated by a deterministic method based on the transfer functions of system components. As the grid frequency is regulated, the deviation can limit high wind power penetration. The research identifies speed governors as one key component in enabling high wind penetration and there is need to factor their increased wear and tear into the ancillary services cost. It also raises the question as to whether the existing standards, set for frequency deviation, which have to be complied at the points of connection of wind energy providers, are adequate to promote high wind penetration.
引用
收藏
页码:708 / 716
页数:9
相关论文
共 12 条
  • [1] *AM WIND EN ASS, 2003, GLOB WIND EN MARK RE, P1
  • [2] *AM WIND EN ASS, 2003, EUR WIND EN ASS GLOB, P3
  • [3] ANDERSON PM, 1994, POWER SYSTEM CONTROL, P38
  • [4] Scheduling and pricing of coupled energy and primary, secondary, and tertiary reserves
    Galiana, FD
    Bouffard, F
    Arroyo, JM
    Restrepo, JF
    [J]. PROCEEDINGS OF THE IEEE, 2005, 93 (11) : 1970 - 1983
  • [5] IEEE Committee Report,, 1973, IEEE T POWER APP SYS, VPAS-92, P1904
  • [6] APPLICATION OF POWER-SYSTEM STABILIZERS FOR ENHANCEMENT OF OVERALL SYSTEM STABILITY
    KUNDUR, P
    KLEIN, M
    ROGERS, GJ
    ZYWNO, MS
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 1989, 4 (02) : 614 - 626
  • [7] PARSONS BK, 1969, IEEE T POWER APP SYS, V88, P1593
  • [8] SAMAD AA, 2004, THESIS U MCGILL MONT
  • [9] WIENER N, 2001, CYBERNETICS
  • [10] 1969, IEEE T POWER APP SYS, V88, P1248