Three-Level Inverter-Based Shunt Active Power Filter in Three-Phase Three-Wire and Four-Wire Systems

被引:194
作者
Vodyakho, Oleg [1 ]
Mi, Chris C. [2 ]
机构
[1] Florida State Univ, Dept Elect & Comp Engn, Tallahassee, FL 32310 USA
[2] Univ Michigan, Dept Elect & Comp Engn, Dearborn, MI 48128 USA
关键词
Direct current control (DCC); multilevel inverters; neutral clamped; power factor correction; power filter; reactive power compensation; shunt active filter; space vector; three-phase four-wire system; voltage-source inverter (VSI); VOLTAGE-SOURCE; COMPENSATION;
D O I
10.1109/TPEL.2009.2016663
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a direct current-space-vector control of an active power filter (APF) based on a three-level neutral-point-clamped (NPC) voltage-source inverter. The proposed method indirectly generates the compensation current reference by using an equivalent conductance of the fundamental component using APF's dc-link voltage control. The proposed control can selectively choose harmonic current components by real-time fast Fourier transform to generate the compensation current. The compensation current is represented in a rotating coordinate system with chosen switching states from a switching table implemented in a field-programmable gate array. In addition, a three-phase four-wire APF based on a three-level neutral-point-clamped inverter is also presented. The proposed APF eliminates harmonics in all three phases as well as the neutral current. A three-phase three-wire NPC inverter system can be used as a three-phase four-wire system since the split dc capacitors provide a neutral connection. To regulate and balance the split dc-capacitor voltages, a new control method using a sign cubical hysteresis controller is proposed. The characteristics of the APF system with an LCL-ripple filter are investigated and compared with traditional current control strategies to evaluate the inherent advantages. The simulation and experimental results validated the feasibility of the proposed APF.
引用
收藏
页码:1350 / 1363
页数:14
相关论文
共 20 条
[1]   Active harmonic filters [J].
Akagi, H .
PROCEEDINGS OF THE IEEE, 2005, 93 (12) :2128-2141
[2]   A control structure for fast harmonics compensation in active filters [J].
Allmeling, J .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2004, 19 (02) :508-514
[3]   Application of discontinuous PWM modulation in active power filters [J].
Asiminoaei, Lucian ;
Rodriguez, Pedro ;
Blaabjerg, Frede .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2008, 23 (04) :1692-1706
[4]  
ASIMINOAEI M, P APEC 2005, V1, P635
[5]   CONSERVATIVE TREATMENT OF CORROSIVE ESOPHAGEAL STRICTURES - A COMPARATIVE-STUDY OF ENDOSCOPIC DILATATIONS AND ESOPHAGEAL STENTING [J].
DEPEPPO, F ;
RIVOSECCHI, M ;
FEDERICI, G ;
MATARAZZO, E ;
PONTICELLI, A ;
SCHINGO, P ;
DALLOGLIO, L .
PEDIATRIC SURGERY INTERNATIONAL, 1993, 8 (01) :2-7
[6]   A three-phase four-wire power filter comprising a three-phase three-wire active power filter and a Zig-Zag transformer [J].
Jou, Hurng-Liahng ;
Wu, Kuen-Der ;
Wu, Jinn-Chang ;
Chiang, Wen-Jung .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2008, 23 (01) :252-259
[7]   Novel Space Vector Based Current Controllers for PWM-Inverters [J].
Kazmierkowski, Marian P. ;
Dzieniakowski, Maciej A. ;
Sulkowski, Waldemar .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 1991, 6 (01) :158-166
[8]   High performance current controller for selective harmonic compensation in active power filters [J].
Lascu, Cristian ;
Asiminoaei, Lucian ;
Boldea, Ion ;
Blaabjerg, Frede .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2007, 22 (05) :1826-1835
[9]   Comparison of control strategies for shunt active power filters in three-phase four-wire systems [J].
Milanes Montero, Maria Isabel ;
Romero Cadaval, Enrique ;
Barrero Gonzalez, Fermin .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2007, 22 (01) :229-236
[10]   Voltage-source active power filter based on multilevel converter and ultracapacitor DC link [J].
Ortúzar, ME ;
Carmi, RE ;
Dixon, JW ;
Morán, L .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2006, 53 (02) :477-485