Numerical investigation of hot air recirculation of air-cooled condensers at a large power plant

被引:72
作者
Liu, Peiqing [1 ]
Duan, Huishen [1 ]
Zhao, Wanli [1 ]
机构
[1] Beijing Univ Aeronaut & Astronaut, Dept Aviat Sci & Engn, Key Lab Fluid Mech Educ Minist, Beijing 100191, Peoples R China
关键词
Hot air recirculation; Air-cooled condenser; Hot recirculation rate; WIND-TUNNEL SIMULATION; FAN PERFORMANCE; HEAT-EXCHANGERS;
D O I
10.1016/j.applthermaleng.2008.09.011
中图分类号
O414.1 [热力学];
学科分类号
摘要
In order to minimize the hot air recirculation (HAR) to ensure normal operation of the air-cooled condensers (ACC) system, the hot air recirculation phenomenon and its dependence on ambient winds are numerically simulated by using the computational fluid dynamics code, FLUENT. Under the constant ambient temperature, the effects of different wind speed and wind direction on the HAR are qualitatively considered by applying the concept of the hot recirculation rate (HRR). The mechanism of occurrence of hot air recirculation are presented and analyzed. It was found that when considering about the existing and normally operating power plants, the HAR is more sensitive to wind direction and wind speed. Based on the above results, two improved measures increasing the wind-wall height and accelerating the rotational speed of the fans near the edge of the ACC platform are developed to effectively reduce the hot air recirculation. (C) 2008 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1927 / 1934
页数:8
相关论文
共 9 条
[1]   Numerical investigation of fan performance in a forced draft air-cooled steam condenser [J].
Bredell, JR ;
Kröger, DG ;
Thiart, GD .
APPLIED THERMAL ENGINEERING, 2006, 26 (8-9) :846-852
[2]   The influence of wind on the performance of forced draught air-cooled heat exchangers [J].
Duvenhage, K ;
Kroger, DG .
JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 1996, 62 (2-3) :259-277
[3]  
Goldschagg H., 1999, Modern Power Systems, V19, P43
[4]   Wind tunnel simulation on re-circulation of air-cooled condensers of a power plant [J].
Gu, ZF ;
Li, H ;
Zhang, WH ;
Li, Y ;
Peng, JY .
JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2005, 93 (06) :509-520
[5]   Wind tunnel simulation of exhaust recirculation in an air-cooling system at a large power plant [J].
Gu, Zhifu ;
Chen, Xuerei ;
Lubitz, William ;
Li, Yan ;
Luo, Wonlin .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2007, 46 (03) :308-317
[6]   Numerical investigation of the effect of fan performance on forced draught air-cooled heat exchanger plenum chamber aerodynamic behaviour [J].
Meyer, CJ ;
Kröger, DG .
APPLIED THERMAL ENGINEERING, 2004, 24 (2-3) :359-371
[7]   EFFECT OF INLET FLOW DISTORTIONS ON FAN PERFORMANCE IN FORCED DRAFT AIR-COOLED HEAT-EXCHANGERS [J].
SALTA, CA ;
KROGER, DG .
HEAT RECOVERY SYSTEMS & CHP, 1995, 15 (06) :555-561
[8]  
VANSTADEN, 1998, P 11 IHTC 6, P155
[9]  
VANSTADEN, 1995, AM SOC MECH ENG FED, V221, P145