Performance study of a doubly fed wind-power induction generator under network disturbances

被引:70
作者
Seman, Slavomir [1 ]
Niiranen, Jouko
Kanerva, Sami
Arkkio, Antero
Saitz, Julius
机构
[1] Helsinki Univ Technol, Lab Electromech, FIN-02015 Helsinki, Finland
[2] ABB Oy, FIN-00381 Helsinki, Finland
[3] Ansoft Corp, Pittsburgh, PA 15219 USA
关键词
coupled model; crowbar; doubly fed induction generator (DFIG); finite-element method (FEM); measurement; voltage dip;
D O I
10.1109/TEC.2005.853741
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Transient performance of a 1.7-MW wind-power doubly fed induction generator (DFIG) under network disturbances is studied using a coupled field-circuit simulator. The simulator consists of the finite-element method model of a DFIG coupled with the circuit model of the frequency converter, a transformer, and a simple model of the network. The simulation results show the transient behavior of the DFIG when a sudden voltage dip is introduced. The field-circuit simulator is experimentally validated by full-power measurement.