An anti-islanding method for single-phase inverters based on a grid voltage sensorless control

被引:110
作者
Liserre, Marco [1 ]
Pigazo, Alberto
Dell'Aquila, Antonio
Moreno, Victor M.
机构
[1] Politecn Bari, I-70125 Bari, Italy
[2] Univ Cantabria, Dept Elect & Comp, Cantabria 39005, Spain
关键词
current control; power systems; pulsewidth-modulated power converters;
D O I
10.1109/TIE.2006.882003
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 [计算机科学与技术];
摘要
The detection of the islanding condition of a distributed generation (DG) system is crucial for safety reasons, as discussed in the IEEE standards and specifically required by some national codes. Several anti-islanding methods that are resident in the inverter have been investigated and classified as passive (measurement of the natural effects of islanding) or active (based on the measurement of the effects due to transients or harmonics deliberately introduced in the system). In case the power drained by the load matches the power generated by the DG inverter, the effect of islanding is small, and the passive methods fail. However, the active methods, which have been developed to overcome these limits, create disturbances that can interact with those generated by other DG systems. In this paper, a new anti-islanding method is proposed. It exploits the natural sensitivity of a grid-voltage sensorless control to disturbances to highlight the islanding condition. The adopted grid-voltage sensorless control is adapted to a single-phase system with the use of resonant controllers based on the internal model control law: resonant-controller-based observer results. Then, a Kalman-filter-based algorithm is used to detect the islanding condition based on the energy mismatch between the estimated third and fifth harmonics and the real ones. Experimental results support the analysis.
引用
收藏
页码:1418 / 1426
页数:9
相关论文
共 22 条
[1]
A novel control method of a VSC without AC line voltage sensors [J].
Agirman, I ;
Blasko, V .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2003, 39 (02) :519-524
[2]
[Anonymous], 1999, SPRINGER SERIES INFO
[3]
[Anonymous], 2003, IEEE Std. 1547-2003, P1
[4]
Sensorless current control for active rectifiers [J].
Bhowmik, S ;
vanZyl, A ;
Spee, R ;
Enslin, JHR .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1997, 33 (03) :765-773
[5]
BLAABJERG F, P APEC, P580
[6]
Brown R.G., 1983, INTRO RANDOM SIGNAL
[7]
Harmonic interaction between a large number of distributed power inverters and the distribution network [J].
Enslin, JHR ;
Heskes, PJM .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2004, 19 (06) :1586-1593
[8]
ESPINOZA R, 2000, P IAS OCT 8 12, V4, P2169
[9]
FUNABASHI T, 2003, P IEEE BOL POW TECH, P6
[10]
HANSEN S, 2000, P IEEE APEC C, V2, P832, DOI DOI 10.1109/TMAG.2004.825025