Study of Fault Current Characteristics of the DFIG Considering Dynamic Response of the RSC

被引:80
作者
Kong, Xiangping [1 ]
Zhang, Zhe [1 ]
Yin, Xianggen [1 ]
Wen, Minghao [1 ]
机构
[1] Huazhong Univ Sci & Technol, State Key Lab Adv Electromagnet Engn & Technol, Wuhan 430074, Peoples R China
基金
中国国家自然科学基金;
关键词
Doubly fed induction generator (DFIG); dynamic response; fault current characteristics; nonsevere fault; FED INDUCTION GENERATOR; WIND TURBINE;
D O I
10.1109/TEC.2014.2309694
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
During nonsevere fault conditions, the crowbar protection is not activated and the rotor windings of a doubly fed induction generator (DFIG) are still excited by the ac/dc/ac converter. In these cases, the dynamic response of a rotor-side converter (RSC) has a large influence on the fault current characteristics of the DFIG. In this paper, an analysis method for the fault current characteristics of the DFIG under nonsevere fault conditions is proposed. First, the dynamic response of the RSC is analyzed on condition that the external power control loop is shut down and the reference signals of the inner rotor current control loop are kept constant. Then, the simplified calculation models of the rotor fault current are established according to different design principles of the inner rotor current controller. Based on it, the fault characteristics of the stator current are studied and the analytical expressions of the stator fault current are obtained. Finally, digital simulation results validate the analytical results. The proposed analysis method is applicable for the study of fault current characteristics of DFIG with different control strategies for low-voltage ride through. The research results are helpful to the construction of adequate relaying protection for the power grid with penetration of DFIGs.
引用
收藏
页码:278 / 287
页数:10
相关论文
共 23 条
[1]  
Abbey C, 2005, P IEEE PES GEN M SAN, V41, P1
[2]  
[Anonymous], 2011, 2011 IEEE POW EN SOC, DOI DOI 10.1109/PES.2011.603892124-29
[3]  
[Anonymous], 2007, NETW SYST RUL GERM T
[4]  
[Anonymous], 2011, 19963 GBT
[5]  
Erickson R. W., 2001, FUNDAMENTALS POWER E, P331
[6]   Improved Sequence Network Model of Wind Turbine Generators for Short-Circuit Studies [J].
Howard, Dustin F. ;
Habetler, Thomas G. ;
Harley, Ronald G. .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2012, 27 (04) :968-977
[7]   An Improved Low-Voltage Ride-Through Control Strategy of Doubly Fed Induction Generator During Grid Faults [J].
Hu, Sheng ;
Lin, Xinchun ;
Kang, Yong ;
Zou, Xudong .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2011, 26 (12) :3653-3665
[8]   Control of DFIG-based wind generation for power network support [J].
Hughes, FM ;
Anaya-Lara, O ;
Jenkins, N ;
Strbac, G .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2005, 20 (04) :1958-1966
[9]  
Jia Junchuan, 2011, Proceedings of the CSEE, V31, P90
[10]  
LEONHARD W, 1995, CONTROL ELECT DRIVES