Numerical simulation for optimizing the design of subway environmental control system

被引:132
作者
Ke, MT [1 ]
Cheng, TC [1 ]
Wang, WP [1 ]
机构
[1] Natl Taiwan Univ Technol, Dept Air Conditioning & Refrigerat, Taipei 106, Taiwan
关键词
computational fluid dynamics; under platform exhaust; piston effect;
D O I
10.1016/S0360-1323(01)00105-6
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Subway Environmental Simulation Program (SES) was used to combine with the commercial computational fluid dynamics (CFD) software to explore the influence of various operating situations to the subway environment of Taipei Rapid Transit System in the present study. The results show that the under platform exhaust (UPE) has a substantial influence on the temperature and the cross-sectional area of the ventilation shaft has quite more effect on the ventilation volume than length. The pressure distribution caused by the piston effect and its effect on the platform screen door was also discussed and compared. (C) 2002 Published by Elsevier Science Ltd.
引用
收藏
页码:1139 / 1152
页数:14
相关论文
共 5 条
  • [1] *ASHRAE, 1999, ASHRAE APPL HDB, pCH28
  • [2] CHENG TC, 2000, THESIS NATL TAIPEI U
  • [3] Tsal R. J., 1987, ASHRAE T, V93, P17
  • [4] 1975, SUBWAY ENV DESIGN HD, V1
  • [5] 1997, SUBWAY ENV DESIGN 1, V2