Extinguishment of cooking oil fires by water mist fire suppression systems

被引:73
作者
Liu, ZG [1 ]
Kim, AK
Carpenter, D
Kanabus-Kaminska, JM
机构
[1] Natl Res Council Canada, Fire Res Program, Ottawa, ON K1A 0R6, Canada
[2] CAFS UNITS Inc, Arcadia, CA 91006 USA
关键词
water mist; fire suppression; cooking oil fire; re-ignition; oil splash;
D O I
10.1023/B:FIRE.0000039161.18616.86
中图分类号
T [工业技术];
学科分类号
08 [工学];
摘要
A series of full-scale experiments were conducted in a mock-up commercial cooking area to study extinguishing mechanisms and effectiveness of water mist against cooking oil fires. The impact of water mist characteristics, such as spray angle, droplet size, flow rate, discharge pressure and type of nozzle, on the effectiveness of water mist against cooking oil fires was investigated. A series of oil splash experiments were also conducted to determine if the oil was splashed by water mist. In addition, the change in oil composition during heating and fire suppression was determined using Fourier Transform Infrared (FTIR) technique. The study showed that cooking oil fires were very difficult to extinguish, because they burned at high temperature and re-ignited easily due to changes in oil composition during heating and fire suppression. The water mist systems developed in the present work effectively extinguished cooking oil fires and prevented them from re-ignition. The spray angle, discharge pressure, and water flow rate were important factors to determine the effectiveness of water mist in extinguishing cooking oil fires.
引用
收藏
页码:309 / 333
页数:25
相关论文
共 31 条
[1]
*ANSUL INC, 1999, 1015 ANSUL INC
[2]
BACK GG, 1994, P HAL ALT TECHN WORK
[3]
*COUNC CAN FIR MAR, 2000, 1997 ANN REP FIR LOS
[4]
Edwards N., 1998, FIRE PREVENTION, V6, P8
[5]
HESKESTAD G, 1995, SFPE HDB FIRE PROTEC, pCH2
[6]
Holman JP., 1992, Heat Transfer
[7]
Effects of PEO length and phenyl unit structure on ionic conductivities of the complexes of LiClO4 and alternating copolymers of PEO having various phenyl units in the backbone [J].
Kim, J ;
Park, MK ;
Bae, JY ;
Ahn, JH .
ELECTROCHEMISTRY COMMUNICATIONS, 2001, 3 (11) :643-648
[8]
KOSEKI H, 2001, P 7 INT FIR MAT C SA, P339
[9]
Lide D. R., 1993, CRC HDB CHEM PHYS
[10]