Classification of Fault and Failure Types Determined by Dissolved Gas Analysis for Transformers

被引:9
作者
Kim, Yonghyun [2 ]
Kweon, Dongjin [2 ]
Park, Taesik [3 ]
Kim, Seonghwan [3 ]
Lim, Jang-Seob [1 ]
机构
[1] Mokpo Natl Maritime Univ, Div Marine Mechatron, Mokpo, South Korea
[2] Kiee Univ, Dept Elect & Elect Engn, Daejeon, South Korea
[3] Mokpo Natl Univ, Dept Elect & Control Engn, Chungnam, South Korea
关键词
Dissolved gas analysis; Failure type; Fault location; Fault type; Internal inspection; Power transformer; PAPER INSULATION; OIL;
D O I
10.1007/s42835-019-00175-0
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
080906 [电磁信息功能材料与结构]; 082806 [农业信息与电气工程];
摘要
In this study, the locations of fault and failure that can be visually identified during internal inspection are determined by classifying the fault and failure types by dissolved gas analysis (DGA). The fault types are classified by analyzing 195 internal inspected transformers that faults were identified, and the failure types are classified by analyzing 338 failed transformers of Korea Electric Power Corporation. The fault types that affected DGA in oil are classified as winding, core, clamp, bushing, on load tap changer (OLTC), and oil. The faults are classified into 18 types according to subcomponent and fault cause. The failure types that affected DGA in oil are classified as winding, bushing, and OLTC. The failures are classified into 21 types according to subcomponent and failure cause. The failure results are classified as turn-to-turn breakdown, breakdown, and oil leakage. The phenomena caused by faults and failures that can be identified by visual during internal inspection are classified as carbon, discharge, and overheat traces.
引用
收藏
页码:1665 / 1674
页数:10
相关论文
共 13 条
[1]
[Anonymous], 2015, document IEC 60599
[2]
[Anonymous], 2014, H00015 KEPCO
[3]
Interpretation of gas-in-oil analysis using new IEC publication 60599 and IEC TC 10 databases [J].
Duval, M ;
dePablo, A .
IEEE ELECTRICAL INSULATION MAGAZINE, 2001, 17 (02) :31-41
[4]
Duval M, 2014, IEEE ELECTR INSUL M, V30, P9, DOI 10.1109/MEI.2014.6943428
[5]
Frequency response of oil impregnated pressboard and paper samples for estimating moisture in transformer insulation [J].
Ekanayake, Chandima ;
Gubanski, Stanislaw M. ;
Graczkowski, Andrzej ;
Walczak, Krzysztof .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (03) :1309-1317
[6]
Electric Technology Research Association, 2009, GUID REF EL POW TRAN, V65
[7]
On the Feasibility of Using Poles Computed from Frequency Domain Spectroscopy to Assess Oil Impregnated Paper Insulation Conditions [J].
Hadjadj, Yazid ;
Meghnefi, Fethi ;
Fofana, Issouf ;
Ezzaidi, Hassan .
ENERGIES, 2013, 6 (04) :2204-2220
[8]
IEEE, 2008, C57104 IEEE
[9]
Kweon D, 2008, DEV MAINTENANCE TECH
[10]
DGA Gases related to the Aging of Power Transformers for Asset Management [J].
Kweon, Dongjin ;
Kim, Yonghyun ;
Park, Taesik ;
Kwak, Nohong ;
Hur, Yongho .
JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2018, 13 (01) :372-378