Contribution of Doubly Fed Wind Generators to Oscillation Damping

被引:158
作者
Tsourakis, Georgios [1 ]
Nomikos, Basil M. [2 ]
Vournas, Costas D. [1 ]
机构
[1] Natl Tech Univ Athens, Sch Elect & Comp Engn, Zografos 15780, Greece
[2] Hellen Transmiss Syst Operator, Piraeus 18545, Greece
关键词
Doubly fed asynchronous generator (DFAG); interarea oscillation damping; power system stabilizer (PSS); small-signal stability; wind power; FED INDUCTION GENERATOR; STABILITY; TURBINE; IMPACT;
D O I
10.1109/TEC.2009.2025330
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this paper, the effects of increased wind power penetration by doubly fed asynchronous generators (DFAGs) on oscillation damping are investigated. With the help of an illustrative example, it is shown that the general trend for DFAGs is to increase interarea oscillation damping. However, there are exceptions for certain penetration levels (not necessarily large), for which the voltage control (VC) option of DFAGs can reduce damping. It is also shown that the modulation of active power generation of wind turbines is a powerful tool to introduce additional damping to interarea oscillations through a simple wind power system stabilizer design. The general trend for increased oscillation damping is verified in the case of a large interconnected system encompassing Southeastern Europe for a projected high level of wind penetration in Greece. For the same system, it is also shown that low-damping voltage oscillations possibly introduced by the VC mode of DFAGs can be adequately damped by properly adjusting control parameters.
引用
收藏
页码:783 / 791
页数:9
相关论文
共 26 条
[1]  
[Anonymous], 2006, GEN TYP 3 WIND TURB
[2]   CONCEPTS OF SYNCHRONOUS MACHINE STABILITY AS AFFECTED BY EXCITATION CONTROL [J].
DEMELLO, FP ;
CONCORDIA, C .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1969, PA88 (04) :316-+
[3]   Comparison of the response of doubly fed and fixed-speed induction generator wind turbines to changes in network frequency [J].
Ekanayake, J ;
Jenkins, N .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2004, 19 (04) :800-802
[4]   Dynamic modeling of doubly fed induction generator wind turbines [J].
Ekanayake, JB ;
Holdsworth, L ;
Wu, XG ;
Jenkins, N .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2003, 18 (02) :803-809
[5]   Modeling of wind turbines based on doubly-fed induction generators for power system stability studies [J].
Erlich, Istvan ;
Kretschmann, Joerg ;
Fortmann, Jens ;
Mueller-Engelhardt, Stephan ;
Wrede, Holger .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (03) :909-919
[6]  
Fan L., 2008, Power and Energy Society General Meeting-Conversion and Delivery of Electrical Energy in the 21st Century, P1
[7]  
Fernandez R.D., 2006, P IEEE POW ENG SOC G
[8]   Large-scale wind power integration in Norway and impact on damping in the Nordic grid [J].
Hagstrom, E ;
Norheim, I ;
Uhlen, K .
WIND ENERGY, 2005, 8 (03) :375-384
[9]   INITIAL RESULTS IN PRONY ANALYSIS OF POWER-SYSTEM RESPONSE SIGNALS [J].
HAUER, JF ;
DEMEURE, CJ ;
SCHARF, LL .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1990, 5 (01) :80-89
[10]   A power system stabilizer for DFIG-based wind generation [J].
Hughes, FM ;
Anaya-Lara, O ;
Jenkins, N ;
Strbac, G .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2006, 21 (02) :763-772