Effect of coil-wire insert on heat transfer enhancement and pressure drop of the horizontal concentric tubes
被引:121
作者:
Naphon, Paisarn
[1
]
机构:
[1] Srinakharinwirot Univ, Fac Engn, Dept Mech Engn, Ongkarak 26120, Nakhon Nayok, Thailand
关键词:
coil-wire insert;
heat transfer enhancement;
pressure drop;
D O I:
10.1016/j.icheatmasstransfer.2006.01.020
中图分类号:
O414.1 [热力学];
学科分类号:
摘要:
In the present study, the heat transfer characteristics and the pressure drop of the horizontal double pipe with coil-wire insert are investigated. The inner and outer diameters of the inner tube are 8.92 and 9.52 mm, respectively. The coiled wire is fabricated by bending a 1 mm diameter of the iron wire into a coil with a coil diameter of 7.80 mm. Cold and hot water are used as working fluids in the shell side and tube side, respectively. The test runs are performed at the cold and hot water mass flow rates ranging between 0.01 and 0.07 kg/s, and between 0.04 and 0.08 kg/s, respectively. The inlet cold and hot water temperatures are between 15 and 20 degrees C, and between 40 and 45 degrees C, respectively. The effect of the coil pitch and relevant parameters on beat transfer characteristics and pressure drop are considered. Coil-wire insert has significant effect on the enhancement of heat transfer especially on laminar flow region. Non-isothermal correlations for the heat transfer coefficient and friction factor are proposed. There is reasonable agreement between the measured data and predicted results. (c) 2006 Elsevier Ltd. All rights reserved.