Protection for DC Distribution System with Distributed Generator

被引:47
作者
Xue, Shimin [1 ]
Chen, Chaochao [1 ]
Jin, Yi [1 ]
Li, Yongli [1 ]
Li, Botong [1 ]
Wang, Ying [2 ]
机构
[1] Tianjin Univ, Key Lab Smart Grid, Minist Educ, Tianjin 300072, Peoples R China
[2] Tianjin Elect Power Corp, Dispatching & Control Ctr, Tianjin 300010, Peoples R China
基金
中国国家自然科学基金;
关键词
SHORT-CIRCUIT; NETWORK;
D O I
10.1155/2014/241070
中图分类号
O29 [应用数学];
学科分类号
070104 [应用数学];
摘要
DC distribution system has advantages of high power quality, large transmission capacity, high reliability, simple structure, economy and low energy consumption, and so forth. It has been a key part of smart grid nowadays. However, the development of DC distribution system is constrained by the lack of operational experience in DC system, the small interrupting capacity of DC circuit breaker (CB), and the lack of protection schemes for system itself. In this paper, protection for DC distribution system with distributed generator (DG) is fully investigated and verified. Firstly, the electromagnetic transient model of DC distribution system with DG is presented. Simulation based on the electromagnetic transient model is carried out. Both the step response and the steady-state performance verify the accuracy of the model. Then the fault characteristic mechanism is analyzed, and the protection principles and scheme are investigated in detail, including voltage mutation principle as protection starting component, differential current protection principle for DC bus, and two-section current protection for distribution lines. Finally, transient responses with protection scheme are analyzed during faults. The results present that the protection principles and scheme are feasible for DC distribution system with DG.
引用
收藏
页数:12
相关论文
共 21 条
[1]
[Anonymous], 2009, 13 EUR C POW EL APPL
[2]
[Anonymous], 2008, P COMP VIS PATT REC
[3]
Overcurrent protection on voltage-source-converter-based multiterminal DC distribution systems [J].
Baran, Mesut E. ;
Mahajan, Nikhil R. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (01) :406-412
[4]
Analysis of high-power IGBT short circuit failures [J].
Barnes, MJ ;
Blackmore, E ;
Wait, GD ;
Lemire-Elmore, J ;
Rablah, B ;
Leyh, G ;
Nguyen, MN ;
Pappas, C .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 2005, 33 (04) :1252-1261
[5]
Byeon G., 2011, 8th International Conference on Power Electronics - ECCE Asia, P543
[6]
Method for Detecting an Open-Switch Fault in a Grid-Connected NPC Inverter System [J].
Choi, Ui-Min ;
Jeong, Hae-Gwang ;
Lee, Kyo-Beum ;
Blaabjerg, Frede .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2012, 27 (06) :2726-2739
[7]
Open-Switch Fault Diagnosis and System Reconfiguration of Doubly fed Wind Power Converter Used in a Microgrid [J].
Duan, Pan ;
Xie, Kai-gui ;
Zhang, Li ;
Rong, Xianliang .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2011, 26 (03) :816-821
[8]
Kakigano H., 2010, 2010 International Power Electronics Conference (IPEC - Sapporo), P480, DOI 10.1109/IPEC.2010.5543501
[9]
Modeling and simulation of a grid-connected PV generation system for electromagnetic transient analysis [J].
Kim, Seul-Ki ;
Jeon, Jin-Hong ;
Cho, Chang-Hee ;
Kim, Eung-Sang ;
Ahn, Jong-Bo .
SOLAR ENERGY, 2009, 83 (05) :664-678
[10]
Design of Smart MVDC Power Grid Protection [J].
Li, Huimin ;
Li, Weilin ;
Luo, Min ;
Monti, Antonello ;
Ponci, Ferdinanda .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2011, 60 (09) :3035-3046