Minimum ignition energy (MIE) - a basic ignition sensitivity parameter in design of intrinsically safe electrical apparatus for explosive dust clouds

被引:48
作者
Eckhoff, RK [1 ]
机构
[1] Univ Bergen, Dept Phys, Proc Technol Programme, N-5007 Bergen, Norway
关键词
dust explosions; minimum ignition energy; ignition curves; intrinsic safety; electrical apparatus;
D O I
10.1016/S0950-4230(02)00003-7
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
In general terms, the purpose of any safety standard is to define borderlines between safe and unsafe conditions, with reasonable safety margins. The electrical spark ignition sensitivity of dust clouds (MIE) varies over at least eight orders of magnitude. Therefore, in the case of intrinsically safe electrical apparatus to be used in the presence of explosive dust clouds, substantial differentiation of the minimum requirements to prevent ignition by electrical sparks is needed. The present paper proposes a method by which adequate differentiation of required maximum permissible currents and/or voltages in intrinsically safe electrical circuits to be used in explosive dust clouds can be achieved. In essence, the concept is to use conservative first-order ignition curves, calculated or estimated from the experimental MIE value of clouds in air of the actual dust. Charts to be used for design purposes are given in the paper. Internationally standardised test methods allow MIE for clouds of any dust to be determined, at least down to the range of a few mJ. There is, however, a need for a supplementary method covering the range of lower energies, down to 0.01 mJ. (C) 2002 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:305 / 310
页数:6
相关论文
共 17 条
[1]  
[Anonymous], 1994, 124123 IEC
[2]  
BARTKNECHT W, EXPLOSIONSSCHUTZ, P93
[3]  
Beck H., 1997, 1397 BIA 1397 BIA
[4]   THE ELECTROSTATIC IGNITIBILITY OF DUST CLOUDS AND POWDERS [J].
BOYLE, AR ;
LLEWELLYN, FJ .
JOURNAL OF THE SOCIETY OF CHEMICAL INDUSTRY-LONDON, 1950, 69 (06) :173-181
[5]  
*CEN, 2001, 13821 PREN CEN
[6]  
*CENELEC, 2000, 50020 EN CENELEC
[7]  
DORSETT HG, 1968, 7132 US DEP INT US B
[8]   Design of electrical equipment for areas containing combustible dust - Why dust standards cannot be extensively harmonised with gas standards [J].
Eckhoff, RK .
JOURNAL OF LOSS PREVENTION IN THE PROCESS INDUSTRIES, 2000, 13 (3-5) :201-208
[9]   WHY ARE LONG ELECTRIC-SPARKS MORE EFFECTIVE DUST EXPLOSION INITIATORS THAN SHORT ONES [J].
ECKHOFF, RK ;
ENSTAD, G .
COMBUSTION AND FLAME, 1976, 27 (01) :129-131
[10]   POSSIBLE SOURCES OF IGNITION OF POTENTIAL EXPLOSIVE GAS ATMOSPHERES ON OFFSHORE PROCESS INSTALLATIONS [J].
ECKHOFF, RK ;
THOMASSEN, O .
JOURNAL OF LOSS PREVENTION IN THE PROCESS INDUSTRIES, 1994, 7 (04) :281-294