Adaptive Distance Relaying Scheme for Transmission Network Connecting Wind Farms

被引:26
作者
Dubey, Rahul K. [1 ]
Samantaray, Subhransu Ranjan [2 ]
Panigrahi, Bijay Ketan [1 ]
机构
[1] Indian Inst Technol, Dept Elect Engn, Delhi, India
[2] Indian Inst Technol, Sch Elect Sci, Bhubaneswar 751013, Orissa, India
关键词
adaptive relay setting; distance relaying; multi-terminal line; transmission line protection; wind farms; power swing; real-time digital simulator; SYMMETRICAL FAULT-DETECTION; DISTRIBUTION-SYSTEMS; PROTECTION; LINES;
D O I
10.1080/15325008.2014.921953
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
080906 [电磁信息功能材料与结构]; 082806 [农业信息与电气工程];
摘要
This article presents an adaptive distance relay setting for a power transmission network connecting more than one wind farm. The ideal trip characteristics of the distance relay is greatly affected in the presence of complex mutual coupling of transmission lines, as the apparent impedance is significantly affected. Similarly, the reach setting of the relay for the lines connecting wind farms is significantly affected, as the relaying voltage fluctuates continuously. Thus, the proposed study focuses on developing an adaptive relay setting for a transmission network including more than one wind farm and considering variations in operating conditions of wind farms and mutual coupling of transmission lines together. The proposed relay algorithm is extensively tested on two-terminal as well as multi-terminal power networks with wide variations in operating parameters. The performance testing of the proposed adaptive relay characteristics for faults and faults during power swing indicates the potential ability of the approach in handling distance relaying in a transmission system.
引用
收藏
页码:1181 / 1193
页数:13
相关论文
共 18 条
[1]
[Anonymous], 2009, COMPUTER RELAYING PO
[2]
High-impedance Faults Analysis in Distribution Networks Using an Adaptive Neuro Fuzzy Inference System [J].
Aziz, M. S. Abdel ;
Hassan, M. A. Moustafa ;
Zahab, E. A. .
ELECTRIC POWER COMPONENTS AND SYSTEMS, 2012, 40 (11) :1300-1318
[3]
Development of adaptive protection scheme for distribution systems with high penetration of distributed generation [J].
Brahma, SM ;
Girgis, AA .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) :56-63
[4]
Wavelet singular entropy-based symmetrical fault-detection and out-of-step protection during power swing [J].
Dubey, Rahul ;
Samantaray, Subhransu Ranjan .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2013, 7 (10) :1123-1134
[5]
Eriksen P. B., 2005, IEEE Power & Energy Magazine, V3, P65, DOI 10.1109/MPAE.2005.1524622
[6]
Digital distance protection of transmission lines in the presence of SSSC [J].
Ghorbani, Amir ;
Mozafari, Babak ;
Ranjbar, Ali Mohammad .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2012, 43 (01) :712-719
[7]
Jongepier G., 1994, IEEE T POWER DELIVER, V9, P1289
[8]
Protection Coordination for Distribution Systems in Presence of Distributed Generators [J].
Kamel, Ahmed ;
Alaam, M. A. ;
Azmy, Ahmed M. ;
Abdelaziz, A. Y. .
ELECTRIC POWER COMPONENTS AND SYSTEMS, 2013, 41 (15) :1555-1566
[9]
Stand alone intelligent digital distance relay [J].
Li, KK ;
Lai, LL ;
David, AK .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2000, 15 (01) :137-142
[10]
Application of Equal Area Criterion Conditions in the Time Domain for Out-of-Step Protection [J].
Paudyal, Sumit ;
Ramakrishna, Gokaraju ;
Sachdev, Mohindar S. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (02) :600-609