Refrigeration assisted spot cooling of a high heat density data center

被引:7
作者
Heydari, A [1 ]
Sabounchi, P [1 ]
机构
[1] Sun Microsyst Inc, Sunnyvale, CA 94086 USA
来源
ITHERM 2004, VOL 1 | 2004年
关键词
data center cooling; evaporator; fan coil; electronic cooling; thermal modeling; refrigeration; CFD;
D O I
10.1109/ITHERM.2004.1319230
中图分类号
O414.1 [热力学];
学科分类号
摘要
Analytical modeling of two kinds of direct expansion refrigeration cooling evaporator and a secondary liquid cooling fan coil heat exchanger is incorporated with computational fluid dynamics (CFD) model to analyze a high heat density electronic-and computer data center installed on a raised floor. Both models incorporate an accurate tube-by-tube thermal hydraulic modeling of the heat exchanger. The refrigeration coil analysis incorporates a multi region heat exchanger analysis for a more precise modeling of two phase refrigerant flow in the evaporator. The single phase secondary loop fan coil heat exchanger modeling uses an effectiveness method for regional modeling of the spot-cooling coil. Using an iterative method, results of the heat exchanger modeling is simultaneously incorporated in the CFD model and an optimal design of spot cooling heat exchanger is developed.