An improved fault ride-through strategy for doubly fed induction generator-based wind turbines

被引:124
作者
Kasem, A. H. [1 ]
El-Saadany, E. F. [1 ]
El-Tamaly, H. H. [2 ]
Wahab, M. A. A. [2 ]
机构
[1] Univ Waterloo, Dept Elect & Comp Engn, Waterloo, ON N2L 3G1, Canada
[2] Minia Univ, Fac Engn, Dept Elect Engn, El Minio, Egypt
关键词
D O I
10.1049/iet-rpg:20070092
中图分类号
X [环境科学、安全科学];
学科分类号
08 [工学]; 0830 [环境科学与工程];
摘要
Keeping the generators operating during transient grid faults becomes an obligation for the bulk wind generation units connected to the transmission network and it is highly desired for distribution wind generators. A proposed scheme is implemented to keep the wind-power DFIG operating during transient grid faults. Challenges imposed on the generator configuration and the control during the fault and recovering periods are presented. A comprehensive time domain model for the DFIG with the decoupled dq controller is implemented using Matlab/Simulink software. Intensive simulation results are discussed to ensure the validity and feasibility of the proposed fault ride through technique. The scheme protects the DFIG components, fulfills the grid code requirements and optimises the hardware added to the generator.
引用
收藏
页码:201 / 214
页数:14
相关论文
共 31 条
[1]
Ackermann T, 2005, WIND POWER IN POWER SYSTEMS, P1, DOI 10.1002/0470012684
[2]
Performance optimization for doubly fed wind power generation systems [J].
Bhowmik, S ;
Spée, R ;
Enslin, JHR .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1999, 35 (04) :949-958
[3]
BOGALECKA E, 1993, IEE CONF PUBL, P224
[4]
Reactive compensation techniques to improve the ride-through capability of wind turbine during disturbance [J].
Chompoo-inwai, C ;
Yingvivatanapong, C ;
Methaprayoon, K ;
Lee, WJ .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2005, 41 (03) :666-672
[5]
DITIRICH A, 2005, P POW EL APPL EUR C
[6]
Eltra, 2000, 74174 ELTR
[7]
*EON NETZ GMBH, 2006, GRID COD REG HIGH EX
[8]
ERLICH I, 2005, P IEEE POW ENG SOC G, P2230
[9]
ERLICH L, 2006, IEEE P PES GEN M JUN
[10]
Fujimitsu M., 2005, P POWERCON 2000 INT, V4-7, P25