Integrated Power Transformer Diagnosis Using Hybrid Fuzzy Dissolved Gas Analysis

被引:8
作者
Liu, Chih-Hsuan [1 ]
Lin, Tung-Bin [1 ]
Yao, Leehter [1 ]
Wang, Shun-Yuan [1 ]
机构
[1] Natl Taipei Univ Technol, Dept Elect Engn, Taipei 10608, Taiwan
关键词
dissolved gas analysis (DGA); substation equipment maintenance and management web system (SEMMWS); fault factor; identifiable factor; INCIPIENT FAULTS; SYSTEM;
D O I
10.1002/tee.22148
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
080906 [电磁信息功能材料与结构]; 082806 [农业信息与电气工程];
摘要
For diagnosing power transformer faults, this study uses hybrid fuzzy technology to integrate five dissolved gas analysis (DGA) approaches: IEEE Standard Doernenburg and Roger ratio methods, IEC60599 Standard ratio method, Electric Technology Research Association of Japan (ETRAJ) Standard ratio method, and Duval triangle method. The IEC TC 10 database and substation equipment maintenance and management web system (SEMMWS) of Taiwan Power Company (TPC) are then used for simulation and verification. Practical cases demonstrate that the integrated approach is more accurate than conventional methods. (c) 2015 Institute of Electrical Engineers of Japan. Published by John Wiley & Sons, Inc.
引用
收藏
页码:689 / 698
页数:10
相关论文
共 18 条
[1]
[Anonymous], 2005, P IEEE PES TRANSM DI
[2]
[Anonymous], 1999, IEC60599
[3]
Interpretation of gas-in-oil analysis using new IEC publication 60599 and IEC TC 10 databases [J].
Duval, M ;
dePablo, A .
IEEE ELECTRICAL INSULATION MAGAZINE, 2001, 17 (02) :31-41
[4]
A comparative study of neural network efficiency in power transformers diagnosis using dissolved gas analysis [J].
Guardado, JL ;
Naredo, JL ;
Moreno, P ;
Fuerte, CR .
IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (04) :643-647
[5]
Developing a new transformer fault diagnosis system through evolutionary fuzzy logic [J].
Huang, YC ;
Yang, HT ;
Huang, CL .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (02) :761-767
[6]
IEEE, 1991, IEEE STANDARD C57, P1
[7]
AN EXPERT SYSTEM FOR TRANSFORMER FAULT-DIAGNOSIS USING DISSOLVED-GAS ANALYSIS [J].
LIN, CE ;
LING, JM ;
HUANG, CL .
IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (01) :231-238
[8]
Mei DH, 2000, IEE CONF PUBL, P192, DOI 10.1049/cp:20000503
[9]
A hybrid tool for detection of incipient faults in transformers based on the dissolved gas analysis of insulating oil [J].
Morais, DR ;
Rolim, JG .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (02) :673-680
[10]
Muhamad NA, 2007, 2007 CONFERENCE PROCEEDINGS IPEC, VOLS 1-3, P1301