Topology Identification and Line Parameter Estimation for Non-PMU Distribution Network: A Numerical Method

被引:191
作者
Zhang, Jiawei [1 ]
Wang, Yi [2 ]
Weng, Yang [3 ]
Zhang, Ning [1 ]
机构
[1] Tsinghua Univ, State Key Lab Power Syst, Dept Elect Engn, Beijing 100084, Peoples R China
[2] Swiss Fed Inst Technol, Power Syst Lab, CH-8092 Zurich, Switzerland
[3] Arizona State Univ, Sch Elect Comp & Energy Engn, Tempe, AZ 85281 USA
基金
中国国家自然科学基金;
关键词
Topology; Network topology; Voltage measurement; Phasor measurement units; Estimation; Smart meters; Mathematical model; Topology identification; state estimation; distribution network; smart meter; data-driven; RENEWABLE ENERGY; SYSTEM;
D O I
10.1109/TSG.2020.2979368
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
080906 [电磁信息功能材料与结构]; 082806 [农业信息与电气工程];
摘要
The energy management system becomes increasingly indispensable with the extensive penetration of new players in the distribution networks, such as renewable energy, storage, and controllable load. Also, the operation optimization of the active distribution system requires information on operation state monitoring. Smart measuring equipment enables the topology identification and branch line parameters estimation from a data-driven perspective. Nevertheless, many current methods require the nodal voltage angles measured by phasor measurement units (PMUs), which might be unrealistic for conventional distribution networks. This paper proposes a numerical method to identify the topology and estimate line parameters without the information of voltage angles. We propose a two-step framework: the first step applies a data-driven regression method to provide a preliminary estimation on the topology and line parameter; the second step utilizes a joint data-and-model-driven method, i.e., a specialized Newton-Raphson iteration and power flow equations, to calculate the line parameter, recover voltage angle and further correct the topology. We test the method on IEEE 33 and 123-bus looped networks with load data from 1000 users in Ireland. The results demonstrate that the proposed method can provide an accurate estimation of the topology and line parameters based on limited samples of measurement without voltage angles.
引用
收藏
页码:4440 / 4453
页数:14
相关论文
共 27 条
[1]
[Anonymous], 2015, ADDING GRADIENT NOIS
[2]
[Anonymous], 2015, DISTRIBUTION SYSTEM
[3]
A survey on control issues in renewable energy integration and microgrid [J].
Badal, Faisal R. ;
Das, Purnima ;
Sarker, Subrata K. ;
Das, Sajal K. .
PROTECTION AND CONTROL OF MODERN POWER SYSTEMS, 2019, 4 (01)
[4]
Bolognani S, 2013, IEEE DECIS CONTR P, P1659, DOI 10.1109/CDC.2013.6760120
[5]
Inverter Probing for Power Distribution Network Topology Processing [J].
Cavraro, Guido ;
Kekatos, Vassilis .
IEEE TRANSACTIONS ON CONTROL OF NETWORK SYSTEMS, 2019, 6 (03) :980-992
[6]
Graph Algorithms for Topology Identification Using Power Grid Probing [J].
Cavraro, Guido ;
Kekatos, Vassilis .
IEEE CONTROL SYSTEMS LETTERS, 2018, 2 (04) :689-694
[7]
Commission for Energy Regulation, 2012, CER SMART MET PROJ E, V1
[8]
Dasgupta K, 2013, IEEE POW ENER SOC GE
[9]
Analysis of power transfer limit considering thermal balance of overhead conductor [J].
Dong, Xiaoming ;
Kang, Chongqing ;
Sun, Hua ;
Zhang, Ning .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2015, 9 (14) :2007-2013
[10]
Greville, 1974, GEN INVERSES THEORY