Applying condensing-temperature control in air-cooled reciprocating water chillers for energy efficiency

被引:57
作者
Chan, KT [1 ]
Yu, FW [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Hong Kong, Peoples R China
关键词
air-cooled chillers; condensing temperature control; head pressure control; energy efficiency;
D O I
10.1016/S0306-2619(02)00053-3
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper reports on the modelling and findings of the energy performance of an air-cooled reciprocating multiple-chiller plant under the conventional head pressure control and the new condensing-temperature control in a subtropical climate, The simulation model was validated using the operating data of an existing chiller plant. As noted from this existing air-cooled reciprocating chiller plant, there as a substantial efficiency drop at part-load resulting from the head pressure control. If operating at variable lower condensing-temperatures based on the established operating mode of the condenser fans and compressors, it is shown that the chiller consumption can be maintained below 2 kW, 1 refrigeration ton throughout the entire range of outdoor temperature and part-load conditions, giving an average efficiency of 1.08 kW/refrigeration ton. The energy imposition due to cycling on more condenser fans can be compensated by the reduced compressor consumption. Potential energy savings of 18.2 and 29% in the annual chiller consumption are achievable by applying the condensing-temperature control to two existing chiller plants studied. This supports the need to develop the condensing-temperature control as an improvement to the conventional head pressure control. (C) 2002 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:565 / 581
页数:17
相关论文
共 19 条
[1]  
ARI, 1998, 550590 ARI
[2]   Steady-state model of centrifugal liquid chillers [J].
Browne, MW ;
Bansal, PK .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1998, 21 (05) :343-358
[3]  
Chan K., 2002, Building Services Engineering Research & Technology, V23, P31, DOI 10.1191/0143624402bt028oa
[4]   Energy impact of commercial-building envelopes in the sub-tropical climate [J].
Chan, KT ;
Chow, WK .
APPLIED ENERGY, 1998, 60 (01) :21-39
[5]  
Deng SM, 2000, BUILD ENVIRON, V35, P603
[6]  
DOSSAT RJ, 1996, PRINCIPLES REFRIGERA
[7]   THERMODYNAMIC MODELING OF RECIPROCATING CHILLERS [J].
GORDON, JM ;
NG, KC .
JOURNAL OF APPLIED PHYSICS, 1994, 75 (06) :2769-2774
[8]  
*GOV HKSAR EL MECH, 1998, COD PRACT EN EFF AIR
[9]  
KEMPIAK MJ, 1992, ASHRAE TRAN, V98, P475
[10]   Design and performance evaluation of reciprocating refrigeration systems [J].
Khan, JUR ;
Zubair, SM .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1999, 22 (03) :235-243