Application studies of superconducting fault current limiters in electric power systems

被引:123
作者
Ye, L [1 ]
Lin, L
Juengst, KP
机构
[1] Forschungszentrum Karlsruhe, Inst Tech Phys, D-76021 Karlsruhe, Germany
[2] Chinese Acad Sci, Inst Elect Engn, Beijing 100080, Peoples R China
关键词
power quality; SFCL; short circuit; superconducting fault current limiter; transient stability;
D O I
10.1109/TASC.2002.1018545
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In power systems, superconducting fault current limiters (SFCLs) can limit the prospective short-circuit currents to lower levels, so that the underrated switchgears can be operated safely. This paper presents a detailed theoretical analysis of improving power system stability by using of SFCLs. Electromagnetic Transient Program (EMTP) simulation results based on a model system also show that SFCLs are effective for enhancing the transient stability of electric power systems by restraining the generator rotors from accelerating after faults and improving power quality. This paper outlines the basic application guidelines for using superconducting fault current limiters in different voltage-level power systems. In order to insure the safe and proper usage of SFCLs, some future considerations on the interaction between SFCLs and power systems are presented as well.
引用
收藏
页码:900 / 903
页数:4
相关论文
共 9 条
[1]  
CHEN M, 1997, FABRICATION CHARACTE, V282
[2]   ASSESSMENT STUDY OF SUPERCONDUCTING FAULT-CURRENT LIMITERS OPERATING AT 77-K [J].
GIESE, RF ;
RUNDE, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (03) :1138-1147
[3]  
Machowski J., 2008, Power System Dynamics: Stability and Control, V2nd
[4]  
PAUL W, 2000, CIGRE, P1
[5]  
POWER AJ, 1995, C FAULT CURR LIM LOO
[6]  
SCHWALL R, 1997, WTEC PANEL REPORT SU
[7]   SOLID-STATE DISTRIBUTION CURRENT LIMITER AND CIRCUIT-BREAKER - APPLICATION REQUIREMENTS AND CONTROL STRATEGIES [J].
SMITH, RK ;
SLADE, PG ;
SARKOZI, M ;
STACEY, EJ ;
BONK, JJ ;
MEHTA, H .
IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (03) :1155-1164
[8]   TOWARDS THE SUPERCONDUCTING FAULT CURRENT LIMITER [J].
THURIES, E ;
PHAM, VD ;
LAUMOND, Y ;
VERHAEGE, T ;
FEVRIER, A ;
COLLET, M ;
BEKHALED, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (02) :801-808
[9]  