Extended Reactive Capability of DFIG Wind Parks for Enhanced System Performance

被引:88
作者
Konopinski, Ryan J. [1 ]
Vijayan, Pradip [1 ]
Ajjarapu, Venkataramana [1 ]
机构
[1] Iowa State Univ, Dept Elect Engn, Ames, IA 50010 USA
关键词
Capability curve; converter ratings; DIgSILENT; doubly fed induction generator (DFIG); FERC regulation; optimal power flow; system dynamics; wind energy; FED INDUCTION GENERATOR; POWER-CONTROL; TURBINE;
D O I
10.1109/TPWRS.2009.2023260
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
080906 [电磁信息功能材料与结构]; 082806 [农业信息与电气工程];
摘要
This paper discusses the impact of utilizing the capability curve of a doubly fed induction generator (DFIG) based wind park on steady state and dynamic power system operation. The interconnection requirements set forth by FERC in order 661-A mandate the operation of wind parks within a power factor range of 0.95 leading and lagging. This operation drastically underutilized the reactive output of the machine. The results presented demonstrate that committing the full reactive capability of a DFIG park for generation dispatch produce a significant reduction in system losses. This additional reactive support was also found to improve post-fault voltage profiles by damping oscillations and preventing overshoots immediately after being subjected to a disturbance. This utilization of extended reactive limits in voltage control may prevent system collapse.
引用
收藏
页码:1346 / 1355
页数:10
相关论文
共 49 条
[1]
*ABB INC EL SYST C, 2005, WIND FARM INT BRIT C
[2]
Abed A. M., 1999, PROC IEEE POWER ENG, V1, P191
[3]
Ajjarapu V., 2006, COMPUTATIONAL TECHNI, P1
[4]
[Anonymous], MATPOWER USERS MANUA
[5]
*AWEA, 2008, LEG AFF
[6]
The renewable portfolio standard: design considerations and an implementation survey [J].
Berry, T ;
Jaccard, M .
ENERGY POLICY, 2001, 29 (04) :263-277
[7]
Bhattacharya K., 2001, IEEE POWER ENG REV, V21, P64, DOI DOI 10.1109/MPER.2001.4311391
[8]
Policies and market factors driving wind power development in the United States [J].
Bird, L ;
Bolinger, M ;
Gagliano, T ;
Wiser, R ;
Brown, M ;
Parsons, B .
ENERGY POLICY, 2005, 33 (11) :1397-1407
[9]
Boldea I, 2016, VARIABLE SPEED GENERATORS, 2ND EDITION, P1
[10]
Chi YN, 2006, 2006 INTERNATIONAL CONFERENCE ON POWER SYSTEMS TECHNOLOGY: POWERCON, VOLS 1- 6, P1133